20
5.3. Parameterization - Nominal current setting
• Press the reset button for more than 6 s to change to the "Parameterization" mode - the green PWR LED
flashes once.
In the Parameterization mode, the LEDs are switched off every 2 s for 0.3 s to distinguish this mode from
other operating modes.
• Set the nominal current of the drive using the
240° potentiometer. The nominal current is spec-
ified in 16 stages. The four LEDs show the set
current.
• Store this value by pressing the reset button
again (non-volatile area of the data memory).
• Press the reset button for more than 2 s (and less
than 6 s) to display the set current for 3 s. This
function is only possible if 1) the device is not ac-
tivated, and 2) there is no defect at the device.
If the motor current is above 45 A, the
block monitoring is activated (see 9.1.
Trigger characteristic curve, and 9.2. De-
rating curve).
6. Application examples
6.1. EMERGENCY STOP
Integrating a hybrid motor starter into an EMERGENCY STOP chain is pictured in Fig. 5 (page 62).
Here, the control voltage supply is switched off via the safety relays, as soon as the EMERGENCY STOP
button is actuated.
Switching off the control voltage supply with a controlled motor always results in wear in
the hybrid motor starter!
This switch should only be used if no more than 10,000 shutdowns can be expected over the entire
lifespan of the system.
If the switch-off is performed, for instance, from a "safe controller" with semiconductor outputs, the resid-
ual voltage must be < 5 V DC. Interruptions
≤
1 ms are filtered.
6.2. Safety door (EMERGENCY STOP)
In applications where the safety switch-off is a normal operating mode, such as in the case of safety door
or two-hand applications, a circuit as per Fig. 6 (page 63) should be used.
In this application, the control circuit is switched and not the control supply voltage.
If the switch-off is performed, for instance, from a "safe controller" with semiconductor outputs, the resid-
ual voltage must be < 5 V DC. Interruptions
≤
3 ms are filtered.
Code
Nominal current [mA]
Variant:
PWR ERR
L
R
0.6 A
2 A
9 A
0
0
0
0
75
180
1500
0
0
0
1
110
250
2000
0
0
1
0
145
410
2500
0
0
1
1
180
560
3000
0
1
0
0
215
710
3500
0
1
0
1
250
870
4000
0
1
1
0
285
1020
4500
0
1
1
1
320
1170
5000
1
0
0
0
355
1330
5500
1
0
0
1
390
1480
6000
1
0
1
0
425
1630
6500
1
0
1
1
460
1790
7000
1
1
0
0
495
1940
7500
1
1
0
1
530
2090
8000
1
1
1
0
565
2250
8500
1
1
1
1
600
2400
9000