Philips IRT 9090 User Manual Download Page 30

 

 

SpaceWise for Industrial Applications 

 

 

v. 1.6 

 

Philips Lighting North America 

 

 

29 

15.

 

FAQs 

A.

 

My  luminaire  group  is  at  low  light  level  and  does  not  respond  to  SpaceWise  remote 
buttons. 

Luminaire may be in an “open” group state. In this state, the luminaire level is at 5% and 
won’t  respond  to  ON/OFF  or  locking  and  unlocking  commands.  Press  the  close  door 
button to close the group. The luminaire will now respond to normal commands.   

 

B.

 

The luminaire light level is high but it is not responding to any commands. Sometimes it 
responds to ON/OFF commands. As a result, I cannot group the luminaires.  

Turn the luminaire OFF using the “OFF” button. Now test the other commands such as 
locking,  unlocking,  open  door  etc.  If  the  luminaire  responds  to  these  commands  then 
finish all the grouping steps.  

If the luminaire is not responding to ON/OFF commands, then perform a power cycle on 
the luminaire either from a wall switch (non SpaceWise switch) or from the breaker panel 
–  turn  the  power  off  for  5  seconds  and  then  turn  it  back  on.  After  a  power  cycle,  the 
luminaire  will  take  30  seconds  to  stabilize.  After  these  30  seconds  test  the  ON/OFF 
commands on the luminaire.  

Please  note  that,  if  power  cycle  is  performed  or  interrupted  in  between  the  grouping 
sequence, then those luminaires that were successfully grouped will be in a locked state 
while  the  remaining  ones  on  that  circuit  will  be  in  the  factory  state  (unlocked).  To 
continue grouping, unlock and open the successful group first.  

 

C.

 

What is the recommended distance between two SpaceWise luminaires? 

Standard  grid  spacing  must  be  maintained  between  luminaires.  It  is  recommended  to 
keep the distance as short as possible but it can be extended up to 20 ft. if other physical 
parameters of the space are conducive for wireless transmission.  

 

D.

 

Do my luminaires forget their settings after power is lost or interrupted? 

No, all settings are retained as long as the luminaires have not been factory reset or there 
has been a hardware failure. 

Summary of Contents for IRT 9090

Page 1: ...t any time without notice or obligation and will not be liable for any consequences resulting from the use of this publication 08 15 philips com luminaires Philips Lighting North America Corporation 200 Franklin Square Drive Somerset NJ 08873 Tel 855 486 2216 Philips Lighting Canada Ltd 281 Hillmount Rd Markham ON Canada L6C 2S3 Tel 800 668 9008 ...

Page 2: ...g zones in a group 15 9 Activate Deactivate occupancy sensor 18 10 Activate Deactivate daylight sensor 20 11 Daylight Calibration 22 12 Test occupancy coverage area walk test 24 13 Path of egress mode for emergency applications 25 14 Troubleshooting 28 15 FAQs 29 16 FCC Compliance Statement 30 17 Warranty 30 18 Technical support 30 This document should only be used for commissioning a SpaceWise In...

Page 3: ...ned specifically to meet the lighting control needs of an industrial space With this technology installers can group multiple luminaires and activate automated dimming behaviors using a SpaceWise remote control A SpaceWise Technology Luminaire contains an integrated MultiSensor which comprises of the following elements A maximum of 50 luminaires can be grouped together using the SpaceWise remote U...

Page 4: ...re sensor coverage area To limit unwanted motion detection the coverage of the luminaire can be restricted by applying a cover The cover is a plastic circular ring sticker that can be peeled and applied on the lens of the sensor In any instance the view of the sensor should not be blocked with any obstructions ...

Page 5: ...r fans and air conditioning outlets will hamper the performance of the sensor and therefore it is important to have a minimum of 6 5 feet distance between air outlets and the luminaire Also check that the first luminaire is in the right position and oriented correctly with respect to the edge of the isle Refer to section 12 walk test for details on testing the coverage area of the sensor Note the ...

Page 6: ...instructions and ensure sensors from adjacent luminaires are not positioned next to one another 3 SpaceWise Remote IRT 9090 The SpaceWise remote is the only tool required by the installer to group the SpaceWise Technology Luminaires together and to change any default configuration settings A set of 2 AAA batteries of 1 5V each are supplied with the remote Before proceeding to the commissioning ins...

Page 7: ...SpaceWise for Industrial Applications v 1 6 Philips Lighting North America 6 ...

Page 8: ...bleshooting before proceeding a Point remote to any luminaire and press Open once Wait for the luminaire to dim down to 5 Make sure the button is pressed only once Pushing multiple times can create multiple networks which can cause undesired operation b Walk to the next luminaire to be added to the group point to the luminaire and press add Repeat step for adding all the luminaires in the group Ad...

Page 9: ...luminaires in the group and press lock Wait for LED to stop blinking apx 10 seconds then press send Red LED on remote will start blinking The luminaire will FLASH twice Group is ready for normal operation Once the group is locked it will not accept any configuration changes To make any changes the group has to be unlocked first In order to save time you can choose to lock the group after finishing...

Page 10: ...finite Infinite Infinite Infinite Infinite Start up and Dim behavior Behavior of the luminaires after grouping Switch ON Level3 60 60 60 60 70 Background Level 10 20 10 20 70 Hold Time 2 min 5 min 2 min 5 min 20 min Fading to Switch ON Level 0s 0s 0s 0s 0s Fading to Background Level 10s 10s 10s 10s 10s Prolong Time 2 min 5 min Infinite Infinite Infinite Switch OFF to 0 Yes Yes No Stays at backgrou...

Page 11: ...res and press send Red LED on remote will start blinking Red LED on remote will stop blinking The luminaire will FLASH twice and group light level will go to 50 b Point to any of the luminaires in the group and press mode While the LED is still blinking red enter the number for the preferred mode see list at step 5 Eg Select 8 for warehouse comfort application mode Red LED on remote will start bli...

Page 12: ...oup light level will go to 50 If unsure about mode selection or remote blinking status then wait for the remote blinking to stop and redo step b c Point to any of the luminaires in the group and press lock Wait for LED to stop blinking apx 10 seconds then press send Red LED on remote will start blinking The luminaire will FLASH twice Group is ready for normal operation ...

Page 13: ...lectances light level preference and energy goals Light output setting Percentage High 100 Medium default 88 Low 77 Minimum 66 a Point remote to any luminaire and press unlock once Wait for LED to stop blinking apx 10 seconds Point remote to any of the luminaires and press send Red LED on remote will start blinking Red LED on remote will stop blinking The luminaire will FLASH twice and group light...

Page 14: ...one step The luminaire may or may not flash at the end of the step depending upon firmware version Note that the default setting is Medium To get to high go one step up To get to Minimum go two steps down Medium to High Will move light output setting from default of 88 to 100 Medium to low Will move light output setting from default of 88 to 77 Low to minimum Will move light output setting from 77...

Page 15: ...ighting North America 14 c Point to any of the luminaires in the group and press lock Wait for LED to stop blinking apx 10 seconds then press send Red LED on remote will start blinking The luminaire will FLASH twice and group is ready for normal operation ...

Page 16: ...the whole group All luminaires within the zone will react in the same way to any sensor in the zone All other luminaires that are in the same group but in a different or no zone will react on the occupancy signal by going to background level Zones can only be created within a group so a group should be created first as per the instructions in section 4 a Point remote to any luminaire and press unl...

Page 17: ...utton is pressed only once Up to 16 zones can be defined and every time the zone button is pressed a new zone creation process is initiated c Walk to the next luminaire to be added to the zone point to the luminaire and press add Repeat step for adding all the luminaires in the zone Added luminaire will go to 50 To create new zones execute steps b and c again Note that a luminaire can only be part...

Page 18: ...ny of the luminaires in the group and press lock Wait for LED to stop blinking apx 10 seconds then press send Red LED on remote will start blinking The luminaire will FLASH twice Group is ready for normal operation g Alternately zones can also be re tested after locking the group Point remote to any of the luminaires in the created zone and press zone Point to the same luminaire and press on or of...

Page 19: ... Wait for LED to stop blinking apx 10 seconds Point remote to any of the luminaires and press send Red LED on remote will start blinking Red LED on remote will stop blinking The luminaire will FLASH twice and group light level will go to 50 b Press pir button While the LED is still blinking red enter the numbers 10 Enable occupancy sensing 12 Disable occupancy sensing lights will stay at 100 Red L...

Page 20: ...ire will FLASH twice and group light level will go to 50 Repeat step b for all the luminaires that need to be reconfigured c Point to any of the luminaires in the group and press lock Wait for LED to stop blinking apx 10 seconds then press send Red LED on remote will start blinking The luminaire will FLASH twice Group is ready for normal operation ...

Page 21: ...unlock once Wait for LED to stop blinking apx 10 seconds Point remote to any of the luminaires and press send Red LED on remote will start blinking Red LED on remote will stop blinking The luminaire will FLASH twice and group light level will go to 50 b Press daylight button While the LED is still blinking red enter the numbers 1 Disable daylight sensing 2 Enable daylight sensing Red LED on remote...

Page 22: ...ire will FLASH twice and group light level will go to 50 Repeat step b for all the luminaires that need to be reconfigured c Point to any of the luminaires in the group and press lock Wait for LED to stop blinking apx 10 seconds then press send Red LED on remote will start blinking The luminaire will FLASH twice Group is ready for normal operation ...

Page 23: ...oint remote to any luminaire and press unlock once Wait for LED to stop blinking apx 10 seconds Point remote to any of the luminaires and press send Red LED on remote will start blinking Red LED on remote will stop blinking The luminaire will FLASH twice and group light level will go to 50 b Point remote to any of the luminaires and adjust the group light level to the required level using the dimm...

Page 24: ...light set point Red LED on remote will blink The entire group will FLASH twice and group light level will go to 50 d Point to any of the luminaires in the group and press lock Wait for LED to stop blinking apx 10 seconds then press send Red LED on remote will start blinking The luminaire will FLASH twice Group is ready for normal operation ...

Page 25: ...0 seconds Point remote to any of the luminaires and press send Red LED on remote will start blinking Red LED on remote will stop blinking The luminaire will FLASH twice and group light level will go to 50 b Point remote to any of the luminaires and press test To stop the test feature press the test button again Test feature is activated users can now walk in the space to estimate the occupancy cov...

Page 26: ...igured as path of egress because of the built in battery capability of the emergency driver and the non reliance on the generator back up system During emergency the battery will bypass the sensors and therefore the luminaire will not shut off automatically When normal power is restored the luminaire will behave like a standard SpaceWise system The path of egress luminaire should be powered on the...

Page 27: ... any of the luminaires and press send Red LED on remote will start blinking Red LED on remote will stop blinking The luminaire will FLASH twice and group light level will go to 50 b Press pir button While the LED is still blinking red enter the numbers 11 Enable path of egress feature 10 Disable path of egress feature Red LED on remote will start blinking Red LED on remote will stop blinking ...

Page 28: ...uminaires that need to be configured with the path of egress feature The luminaire will FLASH twice and group light level will go to 50 c Point to any of the luminaires in the group and press lock Wait for LED to stop blinking apx 10 seconds then press send Red LED on remote will start blinking The luminaire will FLASH twice Group is ready for normal operation ...

Page 29: ...ess unlock once Wait for LED to stop blinking apx 10 seconds Point remote to any of the luminaires and press send Red LED on remote will start blinking Red LED on remote will stop blinking The luminaire will FLASH twice and group light level will go to 50 b Point to any of the luminaires in the group and press reset Once LED stops blinking with remote still pointing to the luminaire in the group p...

Page 30: ...r from a wall switch non SpaceWise switch or from the breaker panel turn the power off for 5 seconds and then turn it back on After a power cycle the luminaire will take 30 seconds to stabilize After these 30 seconds test the ON OFF commands on the luminaire Please note that if power cycle is performed or interrupted in between the grouping sequence then those luminaires that were successfully gro...

Page 31: ...eceived including interference that may cause undesired operation Any changes or modification not expressly approved by Philips could void the user s authority to operate this equipment This product is intended for commercial use only 17 Warranty A detailed product warranty statement can be found on the Philips website http www lighting philips com us_en connect tools_literature warranties wpd 18 ...

Page 32: ...t any time without notice or obligation and will not be liable for any consequences resulting from the use of this publication 08 15 philips com luminaires Philips Lighting North America Corporation 200 Franklin Square Drive Somerset NJ 08873 Tel 855 486 2216 Philips Lighting Canada Ltd 281 Hillmount Rd Markham ON Canada L6C 2S3 Tel 800 668 9008 ...