troubleshooting 

 

 

DRC810DT Installation Manual Rev I.docx

   9

 

Check the following list.  If you are still unable to rectify the situation, contact your nearest Dynalite dealer.  A 
complete list of distributors worldwide can be found on the Internet at: 

www.philips.com/dynalite

 

Please ensure that you have completed the following prior to calling our technical support department. 
 

 

Check all symptoms in the Troubleshooting list 

 

Check for any deviations between the installation and the installation instructions 

 

Make a list of the model numbers of all devices used in the system 

 

 

SYMPTOM 

PROBABLE CAUSE 

ACTION 

Load Controller does not operate at all. No Service 
LED  activity.  Power  supply  indicator  LED  on  PCB 
not lit. 

Incorrect  connection  of  Mains  supply,  or  no 
power available. 

Check  power  supply  to  Load  Controller.    Check 
Line and Neutral input connections. 

Power supply indicator LED lit, but no Service LED 
activity. 

Supply  voltage  too  low,  short  circuit  on 
network.  Control PCB faulty. 

Check  supply  voltage  is  at  least  75%  of  rated 
voltage.    Check  5V  &  12V  terminal  voltages,  5V 
supply must be present. Disconnect network bus 
and restore power.  Replace control PCB. 

Load  Controller  will  not  respond  to  control  panel 
push buttons. 

Control  panel  incorrectly  wired  or  incorrect 
configuration. 

Check operation of LEDs on control panel.  Push 
button  on  panel  and  study  response  of  service 
LED. 

Load  Controller  operates  properly  but  circuit 
breakers keep tripping. 

Instant tripping: - short circuit on load.  
Delayed tripping: - Load Controller overloaded. 

Check load wiring for short circuits. 
Verify Load Controller loading with current tester 
(don’t forget to de-rate for low power-factor loads 
and  transformer  losses).  Check  that  the  breaker 
terminals are tight. 

Fluorescent lights won’t dim. 

Wrong  type  of  ballast  or  ballast  incorrectly 
wired.  Control  cable  from  DRC810DT  to 
ballasts not installed. 

Check  ballast type.    Check  actual  wiring  against 
ballast manufacturer’s diagram. Check 1-10V/DSI 
cable and settings. 

 

product specifications 

 

 

Supply: 

230V ±14% 50/60Hz Single Phase at 0.1A 

Outputs: 

8 x SPDT voltage free changeover contacts rated at 10 Amps resistive

 

Maximum Total Box Load: 

80A 

Switching Device: 

Relay - NO contact: 10A resistive TV8 rated, NC contact: 10A resistive TV3 rated 

Control Inputs: 

1 x RS485 DyNet/DMX512 serial port 
1 x programmable dry contact AUX input 
8 x multifunction dry contact or analogue inputs 

User Controls: 

Service Switch 
Diagnostic LED 

Internal Controls:  

Programmable Logic Controller 
Dynalite Accessory Module enabled 

DyNet DC VE: 

120mA (supply for approx. 6 Panels) 

Preset Scenes: 

170 

Supply Terminals: 

Line, Neutral – 1 x 4mm

2

 max conductor size 

Output Terminals: 

C, NO, NC for each channel 
1 x 2.5mm

2

 

max conductor size 

Earth link bar provided

 

Cable Entries: 

Mains – 1 x 75mm x 53mm removable gland plate 
Data – 1 x 25mm dia. knockout 

Diagnostic Functions: 

 

Device Online/Offline status 
Circuit run time tracking (optional) 

Compliance: 

CE, C-Tick 

Construction: 

Alloy/Steel wall mount case with epoxy finish 

Dimensions: 

Height 320mm x Width 225mm x Depth 75mm (excludes wall brackets) 

Weight: 

3.5 Kilograms 

Summary of Contents for Dynalite DRC810DT

Page 1: ... 61 2 8338 9333 dynalite info philips com dynalite online com DRC810DT SPDT Dry Contact Relay Controller Installation Manual contents Warning 2 Hardware Controls 8 Features 2 Troubleshooting 9 Important Safeguards 2 Specification 9 Internal View 3 Mounting 4 Supply Load Cable Connections 5 Connecting Serial Control Cables 6 ...

Page 2: ...n cause MCB and terminal block screws to become loose Power Sources This device should only be operated from the type of supply specified on the front panel This device must be earthed Output Circuits The load on a circuit should not exceed the specified capacity of 10A Loads should be calculated to ensure that the overall maximum capacity of 80A is not exceeded Functional isolation only exists be...

Page 3: ... Mounting Point Network Socket Service Switch Depth 75mm Transformer SHLD GND D D 12V AUX Alternative Mounting Point to Enable Easy Cable Access Relay SPDT Dry Contact Outputs EARTH LINK 8 C NO NC 7 C NO NC 6 C NO NC Dry Contact Control Inputs Accessory Socket Supply 230V AC 0 5A LINE IN NEUTRAL For spare parts or service please call your local Philips Dynalite Dealer and specify DRC810DT ...

Page 4: ... brackets are designed to accommodate 4 fixing screws up to 8mm diameter The DRC810DT can be fixed to the wall without opening the cabinet or removing covers Make sure no dust or other debris enters the device during installation Do not leave the front cover off for any length of time Excessive dust and dirt can degrade the cooling of internal components Allow for Cable Entry Supply load and load ...

Page 5: ...uit is not overloaded Calculate the intended load and ensure that it is below the maximum capacity of an individual channel which is 10A resistive Derate for reactive loads When connecting ELV or SELV cables to the relay terminals ensure that proper segregation is maintained between them and mains cables Control Input Cables There are 8 control inputs that terminate on a 10 way terminal strip They...

Page 6: ...leled for VE and one pair used for DATA and DATA Recommended Cable Colour Coding Green White pair paralleled for GND Orange White pair paralleled for VE Blue White pair Blue for DATA White for DATA Brown White pair Spare or for Join The colour coding scheme used is not critical as long as the same scheme is used throughout the installation Serial Cable Connecting Method The recommended connecting ...

Page 7: ...tion Go Stop Motor 1 Motor 2 Motor 3 Motor 4 Example of load wiring for 12V DC bi directional curtain motors Direction Movement Motor 1 Channel 1 2 Motor 2 Channel 3 4 Motor 3 Channel 5 6 Motor 4 Channel 7 8 12V Motor 12V Motor 12V Motor 12V Motor 12V DC Power Supply C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC 8 7 6 5 4 3 2 1 Direction Movement Motor 1 Channel 1 Channel 5 Motor...

Page 8: ...l strip is no longer than 2 metres Service LED The Service LED has 3 signalling modes which are useful for troubleshooting Blinking slowly 1Hz Normal Operation Blinking fast 4Hz Network Activity Detected On Fault Service Switch The Service Switch has three functions 1 push Transmit Network ID 3 pushes All Channels 100 Push hold for 4 sec Reboot Accessory Module Socket Accepts plug in modules for o...

Page 9: ...stant tripping short circuit on load Delayed tripping Load Controller overloaded Check load wiring for short circuits Verify Load Controller loading with current tester don t forget to de rate for low power factor loads and transformer losses Check that the breaker terminals are tight Fluorescent lights won t dim Wrong type of ballast or ballast incorrectly wired Control cable from DRC810DT to bal...

Page 10: ...3 097 246 921 All rights reserved Dynalite Dimtek DyNet and DLight and associated logos are the registered trademarks of Dynalite Intelligent Light Pty Ltd Not to be reproduced without permission Unit 6 691 Gardeners Road Mascot NSW 2020 Australia Tel 61 2 8338 9899 Fax 61 2 8338 9333 E mail dynalite info philips com Web Philips com dynalite ...