6

   

DRC810DT Installation Manual Rev I.docx

 

 
     

 
Determine Your Requirements

 

Serial  Ports  are  used  to  interconnect  other 
dimmers,  smart  control  panels,  sensors  and 
AV  controllers.    Serial  port  devices  can  be 
identified  by  4  terminals,  labelled:  GND, 
DATA + DATA -, +VE. 
 

Serial Cable Connections 

There is one RS485 port for DyNet signals, in 
the form of a RJ12 socket, on the front panel, 
which is used for the temporary connection of 
a  PC  or  a  Portable  Programmer.  There  are 
data  terminals  on  the  control  card,  for 
permanent  connections.    The  recommended 
cable  for  connections  to  the  serial  port  is 
screened,  stranded  RS485  data  cable  with 
three  twisted  pairs.  Recommended  cable 
types include: 

Belden:   

9503 

Garland:   

MCP3S 

Hartland:   

HCK603 

M&M Cable: 

B2003CS 

M&M Cable: 

B9503CS 

Multicables: 

AWM E120236 2092 20 

RS Components: 

368-687 

One  pair  is  paralleled  for  GND,  one  pair  paralleled  for  +VE, 
and one pair used for DATA and DATA.  

 

Recommended Cable Colour Coding 

Green/White pair 

paralleled for GND 

Orange/White pair 

paralleled for +VE 

Blue/White pair 

Blue for DATA + 

 

 

 

White for DATA - 

Brown/White pair 

Spare or for Join  

 
The colour-coding scheme used is not critical, 
as  long  as  the  same  scheme  is  used 
throughout the installation. 
 

Serial Cable Connecting Method 

The  recommended  connecting  method  is  to 
‘daisy  chain’  devices  (ie.  starting  at  the  first 
device,  then  looping  in  then  out  of  devices, 
with  a  single  cable  terminating  at  the  last 
device.  There  should  not  be  any  spurs  or 
stubs,  and  only  the  first  and  last  device 
should  terminate  1  cable,  all  other  devices 
should  terminate  2  cables).  Devices  may  be 
wired  in  any  order.    The  Data  Cable  should 
be  segregated  from  any  Mains  Cables  by 
30mm.  

A data cable that is connected to an 

energised  dimmer  is  live.  Do  not  cut  or 
terminate  live  data  cables

.    If  the  data  cable 

has to cross over any mains cables, it should 
do so at a 90° angle. 

 

Serial Cable Permanent Connections 

 

 

 

 

 

 

Connect Data Cable in a ‘Daisy Chain’ 

RJ12 Socket Connections 

Summary of Contents for Dynalite DRC810DT

Page 1: ... 61 2 8338 9333 dynalite info philips com dynalite online com DRC810DT SPDT Dry Contact Relay Controller Installation Manual contents Warning 2 Hardware Controls 8 Features 2 Troubleshooting 9 Important Safeguards 2 Specification 9 Internal View 3 Mounting 4 Supply Load Cable Connections 5 Connecting Serial Control Cables 6 ...

Page 2: ...n cause MCB and terminal block screws to become loose Power Sources This device should only be operated from the type of supply specified on the front panel This device must be earthed Output Circuits The load on a circuit should not exceed the specified capacity of 10A Loads should be calculated to ensure that the overall maximum capacity of 80A is not exceeded Functional isolation only exists be...

Page 3: ... Mounting Point Network Socket Service Switch Depth 75mm Transformer SHLD GND D D 12V AUX Alternative Mounting Point to Enable Easy Cable Access Relay SPDT Dry Contact Outputs EARTH LINK 8 C NO NC 7 C NO NC 6 C NO NC Dry Contact Control Inputs Accessory Socket Supply 230V AC 0 5A LINE IN NEUTRAL For spare parts or service please call your local Philips Dynalite Dealer and specify DRC810DT ...

Page 4: ... brackets are designed to accommodate 4 fixing screws up to 8mm diameter The DRC810DT can be fixed to the wall without opening the cabinet or removing covers Make sure no dust or other debris enters the device during installation Do not leave the front cover off for any length of time Excessive dust and dirt can degrade the cooling of internal components Allow for Cable Entry Supply load and load ...

Page 5: ...uit is not overloaded Calculate the intended load and ensure that it is below the maximum capacity of an individual channel which is 10A resistive Derate for reactive loads When connecting ELV or SELV cables to the relay terminals ensure that proper segregation is maintained between them and mains cables Control Input Cables There are 8 control inputs that terminate on a 10 way terminal strip They...

Page 6: ...leled for VE and one pair used for DATA and DATA Recommended Cable Colour Coding Green White pair paralleled for GND Orange White pair paralleled for VE Blue White pair Blue for DATA White for DATA Brown White pair Spare or for Join The colour coding scheme used is not critical as long as the same scheme is used throughout the installation Serial Cable Connecting Method The recommended connecting ...

Page 7: ...tion Go Stop Motor 1 Motor 2 Motor 3 Motor 4 Example of load wiring for 12V DC bi directional curtain motors Direction Movement Motor 1 Channel 1 2 Motor 2 Channel 3 4 Motor 3 Channel 5 6 Motor 4 Channel 7 8 12V Motor 12V Motor 12V Motor 12V Motor 12V DC Power Supply C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC 8 7 6 5 4 3 2 1 Direction Movement Motor 1 Channel 1 Channel 5 Motor...

Page 8: ...l strip is no longer than 2 metres Service LED The Service LED has 3 signalling modes which are useful for troubleshooting Blinking slowly 1Hz Normal Operation Blinking fast 4Hz Network Activity Detected On Fault Service Switch The Service Switch has three functions 1 push Transmit Network ID 3 pushes All Channels 100 Push hold for 4 sec Reboot Accessory Module Socket Accepts plug in modules for o...

Page 9: ...stant tripping short circuit on load Delayed tripping Load Controller overloaded Check load wiring for short circuits Verify Load Controller loading with current tester don t forget to de rate for low power factor loads and transformer losses Check that the breaker terminals are tight Fluorescent lights won t dim Wrong type of ballast or ballast incorrectly wired Control cable from DRC810DT to bal...

Page 10: ...3 097 246 921 All rights reserved Dynalite Dimtek DyNet and DLight and associated logos are the registered trademarks of Dynalite Intelligent Light Pty Ltd Not to be reproduced without permission Unit 6 691 Gardeners Road Mascot NSW 2020 Australia Tel 61 2 8338 9899 Fax 61 2 8338 9333 E mail dynalite info philips com Web Philips com dynalite ...

Reviews: