background image

 

 

Philips Lighting North America Corporation 
200 Franklin Square Drive 
Somerset, NJ  08873, USA 
Phone:  855-486-2216 

www.philips.com/luminaires

  

Philips Lighting Canada Ltd. 
281 Hillmount Road, 
Markham ON, Canada  L6C 2S3 
Phone:  800-668-9008 

www.philips.com/luminaires

 

9140053340 

February 2016 

GENERAL INSTRUCTIONS 

 

1)

 

Begin 

the 

installation 

process 

by 

determining mounting options. 

2)

 

The slotted, circular keyways can be used to 
secure  the  mounting  plate  to  a  standard 
junction  box.    The  junction  box  must  be 
secured  sufficiently  to  handle  the  weight  of 
the unit.   

3)

 

Additionally,  three  slotted  vertical  keyway 
slots  (Figure  1)  may  be  used  to  attach  the 
mounting  plate  to  independent  anchor 
supports.    Use  three  #8  toggle  bolts 
(supplied  by  others)  for  securing  to 
wallboard  or  hollow  concrete  walls.  If  the 
wiring  is  wall  recessed,  run  wires  through 
center hole of mounting plate in preparation 
for unit wiring.   

4)

 

If  desired,  wall  mounting  can  also  be 
accomplished  with  use  of  the  optional 
mounting  shelf  (See  Optional  Mounting 
Shelf and Figure 2). 

 

Figure 1

 

HOOKUP INSTRUCTIONS 

 
Standard Units: 

 

Connect A.C. service to unit charger leads:   
Blue = 277 VAC 

 

Black = 120 VAC 

 

White = Common 

 

Green = Ground 

 

  
 

1.

 

Connect  remote  lamps,  if  applicable,  to 
orange and yellow flying leads connected to 
RL+ and RL- respectively.  Ensure total unit  
load  (including  internal  lamps)  does  not 
exceed unit rating. 

2.

 

Adjust head(s) to illuminate desired area(s). 

3.

 

Close  cover  and  screw  shut.    Ensure 
electrical  wires  and  membrane  switch  cable 
remain  inside  unit  and  that  the  cover  does 
not  pinch  wires  when  closed.    Hand-tighten 
two thumb nuts to finalize cover closure.   

INSTALLING BATTERIES 

 

1.

 

Units  may  ship  without  batteries  installed 
depending  on  the  wattage  of  the  unit.    For 
lead  units,  battery  wiring  harnesses  are 
already  connected  to  PCB  assembly  and 
connection  to  the  batteries  is  required.    In 
the  case  of  Nicad  units,  connection  of 
battery harness to the PCB is required.   

2.

 

Install  and  wire  batteries  as  appropriate. 
(See Page 5 for battery configurations) 

3.

 

Tighten straps to secure batteries inside unit. 
 

OPTIONAL MOUNTING SHELF 

 
1.

 

If  the  unit  is  to  be  mounted  to  poles, 
columns  or  I-Beams,  use  the  optional 
mounting  shelf  and  strapping  kit  (ordered 
separately). 

 

 

Figure 2

 

2.

 

Once mounting shelf is  installed, the unit is 
ready for installation. 

 

3.

 

Place unit on shelf and secure with three (3) 
securing  screws  (supplied  with  mounting 
shelf) to shelf threaded inserts.

 

 

 

Summary of Contents for CMFIC Series

Page 1: ...ecommended by the manufacturer may cause an unsafe condition Do not use this equipment for other than intended use Do not use outdoors Do not let supply cords touch hot surfaces Do not mount near gas or electric heaters CAUTION Halogen cycle lamp s are used in this equipment To avoid shattering Do not operate lamp in excess of rated voltage protect lamp against abrasion and scratches and against l...

Page 2: ...it charger leads Blue 277 VAC Black 120 VAC White Common Green Ground 1 Connect remote lamps if applicable to orange and yellow flying leads connected to RL and RL respectively Ensure total unit load including internal lamps does not exceed unit rating 2 Adjust head s to illuminate desired area s 3 Close cover and screw shut Ensure electrical wires and membrane switch cable remain inside unit and ...

Page 3: ...ally initiated diagnostic test Red LED indicator Single Flash battery fault Two Flashes lamp failure light bar failure EXIT signs Three Flashes charger fault Four Flashes transfer fault If more than one fault condition is present simultaneously the red LED will flash the indication pattern for each fault independently then repeat the cycle Pushbutton Test Switch Long Press longer than 0 5sec trans...

Page 4: ...1 Hillmount Road Markham ON Canada L6C 2S3 Phone 800 668 9008 www philips com luminaires 9140053340 February 2016 OPTIONAL REMOTE CONTROL Front Press appropriate button to perform the indicated test or silence the audible alarm Cancel stops any test currently in process Back Explanation of indicator light flash sequences Refer to Table 2 above for further information ...

Page 5: ...lips com luminaires Philips Lighting Canada Ltd 281 Hillmount Road Markham ON Canada L6C 2S3 Phone 800 668 9008 www philips com luminaires 9140053340 February 2016 BATTERY HOOKUP DIAGRAMS LEAD BATTERY HOOKUP 6V 25W LEAD 6V 50W LEAD 12V 50W LEAD NICAD BATTERY HOOKUP 6V 25W NICAD 6V 50W NICAD 12V 25W NICAD 12V 50W NICAD ...