background image

GENERAL

o

These  luminaires  are  used  indoors 

(

ta  40 C

)

 

where  emergency  light  is  needed.

 

Each 

luminaire  must  be  connected  permanently  to 
the mains power supply.

 

ADDRESS OPERATION

The luminaires can be connected to a 
G R - 6 5 0 0   a d d r e s s   p a n e l .   F o r   a d d r e s s  
operations  refer  to  the  installation  manual  of 
the  panel.For  address  module  connections 
see  page 

4

.  For  dip-switch  addressing 

selection see page 

5

 and 

6

.

OPERATION DESCRIPTION 

When the unit is connected to the mains power 
supply  (after  connecting  the  battery)  the 
indicator LAMP FAULT – BATT. FAULT remains 
OFF whereas the indicator POWER CHARGE 
blinks to indicate that the batteries are charging. 
When  the  batteries  are  fully  charged  this 
indicator will light permanently. If this indicator 
does not light then probably the battery has not 
been connected. If the batteries are connected 
and the indicator does not light then contact a 
qualified service technician for assistance. The 
charging  procedure  is  monitored  by  a 
microprocessor and is based on a 3 stage cycle 

thus  ensuring  a  fast  and  full  charge  of  the 
battery. The charge current is supplied by a high 
efficiency  switch  mode  power  supply  which 
ensures  perfect  charging  even  during  the 
fluctuations of the mains power supply.

BATTERY CUTOFF

The  unit  enters  this  state  during  the  power 
supply  failure  and  when  the  battery  has  been 
fully discharged. In this state the luminaire draws 
the  least  power  from  the  battery  in  order  to 
prevent 
deep discharge.

MANUAL TESTING

Is accomplished by briefly (<1 sec.) pressing the 
TEST button. This permits   the user to test the 
good  operation  of  the  luminaire’s  emergency 
circuit.

 

The  unit  simulates  a  power  failure  and 

the lamps are lit using the batteries. This manual 
test does not affect the automatic test

.

DIMMING OPTION

When the 

luminaire is in emergency mode

, with 

corresponding press

ing

s of the button,

 

we ca

n

 

choose 

the illumination of 100%, 50%, 33% 

 or 

turned off

, either to increase the autonomy time 

or  not  to  consume 

the 

battery  power 

unnecessarily. This option is canceled when the 
network is restored.

Thank you for your trust in our products  

Olympia Electronics -  European manufacturer

Page

 1 

from

 7

923039005_09_00

7

ABS/PC, PC

OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY

EXTERNAL DIMENSIONS 

CONSTRUCTION MATERIALS 

TYPICAL WEIGHT
GUARANTEE 

OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Pb)

CHARGING TIME

INDICATIONS - CONTROLS

BATTERY PROTECTION

MINIMUM AUTONOMOUS DURATION

DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH

EMERGENCY ILLUMINATION

LIGHT SOURCE

<24h

POWER-CHARGE indicator, LAMP FAULT–BATT. FAULT indicator, TEST button

From overcharge and deep discharge

IP42

o

5 to 40  C

Up to 95% 

3 years 

(1 

year for the battery

)

180 min

EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3

302 x 94 x 345 mm

220-240V AC/50-60Hz

12V/7Ah

1

3.5

W/14.1VA

3560gr.

  2000lm 

  White LEDs

GRL-39/ADR

TECHNICAL CHARACTERISTICS

 

(

for LED MODULE Specifications see page 

4

)

ADDRESSABLE SELF TESTING

NON MAINTAINED EMERGENCY LUMINAIRE

Summary of Contents for GRL-39/ADR

Page 1: ...least power from the battery in order to prevent deep discharge MANUALTESTING Is accomplished by briefly 1 sec pressing the TEST button This permits the user to test the good operation of the luminaire s emergency circuit The unit simulates a power failure and the lamps are lit using the batteries This manual test does not affect the automatic test DIMMING OPTION When the luminaire is in emergency...

Page 2: ...rect then the fault indicator will light when the power is restored ERASING ERRORS Erasing errors is accomplished with a prolonged pressing of the TEST button 5 sec when the unit is connected to the mains power supply The fault indicated with the indicator LAMP FAULT BATT FAULT will be erased If the cause of the fault has not been restored i e burned lamp then the indicator will light again If the...

Page 3: ...tic cover by fastening the 4 mounting screws tightening torque 1N m NOTE After finishing the installation you must power the luminaire at least for 24 hours for battery charging to perform the nominal autonomy INSTALLATION PROCEDURE For wall mounting only Page 3 from 7 923039005_09_007 INDICATION LED STATUS with the mains power supply connected TEST button Cover retaining screws Fig 1 Fig 2 LAMP F...

Page 4: ...d 0 Non Maintained A Including test device B Including remote rest mode C Including inhibiting mode F Automatic test gear complying with IEC 61347 2 7 denoted EL T 180 3 hours duration 11 Connect the address cables in the terminal block with the indicating polarity Fig 3 12 Address the luminaire by using the dip switches with the appropriate combinations as you can see in pages 5 and 6 Fig 3 Addre...

Page 5: ... 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 ...

Page 6: ...8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON ON 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 ...

Page 7: ...ovided or has any repairs or re setting done by a third party unless Olympia Electronics has fully agreed to them in writing Products that have been damaged can be returned to the premises of our company for repair or replacement as long as the warranty period is valid Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the ...

Reviews: