``POWER LIGHT`` SERIES FOR WATERPROOF ADDRESSABLE SELF TESTING NON MAINTAINED EMERGENCY LUMINAIRES
Bayblend FR3010
,
transparent
polycarbonate
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS
CONSTRUCTION MATERIALS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Pb)
CHARGING TIME
INDICATIONS
-
CONTROLS
BATTERY PROTECTION
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
EMERGENCY ILLUMINATION
LIGHT SOURCE
<24h
POWER
-
CHARGE indicator, LAMP
FAULT
–
BATT
.
FAULT indicator, TEST button
From overcharge and deep discharge
IP65
o
5 to 40 C
Up to 95%
3 years
(1
year for the lamps and the battery
)
180 min
90 min
EN 60598-1, EN 60598-2-22
, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
307 x 100 x 333 mm
220-240V AC/50-60Hz
12V/7Ah
2x12V/7Ah
12V/7Ah
16VA
3770gr.
4260gr.
6450gr.
GENERAL
o
These luminaires are used indoors
(
ta 40 C
)
where emergency light is needed.
Each
luminaire must be connected permanently to
the mains power supply.
ADDRESS OPERATION
The luminaires can be connected to a GR-
6500 address panel. For address operations
refer to the installation manual of the
panel.For address module connections see
page 3. For dip-switch addressing selection
see page 3, 4 and 5.
OPERATION DESCRIPTION
When the unit is connected to the main power
supply (after connecting the battery) the
indicator LAMP FAULT – BATT. FAULT remains
OFF whereas the indicator POWER CHARGE
blinks to indicate that the batteries are
charging. When the batteries are fully charged
this indicator will light permanently. If this
indicator does not light then probably the
battery has not been connected. If the batteries
are connected and the indicator does not light
then contact a qualified service technician for
assistance. The charging procedure is
monitored by a microprocessor and is based on
a 3 stage cycle thus ensuring a fast and full
charge of the battery. The charge current is
supplied by a high efficiency switch mode
power supply which ensures perfect charging
even during the fluctuations of the mains power
supply.
BATTERY CUTOFF
The unit enters this state during the power
supply failure and when the battery has been
fully discharged. In this state the luminaire
draws the least power from the battery in order
to prevent deep discharge.
MANUAL TESTING
Is accomplished by briefly (<1 sec.) pressing the
TEST button. This permits the user to test the
good operation of the luminaire’s emergency
circuit.
The unit simulates a power failure and
the lamps are lit using the batteries. This manual
test does not affect the automatic test
.
DIMMING OPTION
When the voltage is interrupted, with
corresponding press
ing
s of the button,
we ca
n
choose
the illumination of 100%, 50%, 33%
or
turned off
, either to increase the autonomy time
or not to consume
the
battery power
unnecessarily. This option is canceled when the
power
network is restored.
LAMP TESTING
The luminaire tests the good condition of the
lamps in emergency mode and warns the user
for probable malfunction. If a lamp is found faulty
then the LAMP FAULT indicator starts to blink.
To verify which lamp is faulty use the TEST
button. If the faulty lamp is replaced then the
Page
1
from
6
923039006_09_001
1620lm
3200lm
White LEDs
White power LEDs
GRL-39/WP/ADR
GRL-37/180/WP/ADR
GRL-37/90/WP/ADR
Thank you for your trust in our products
Olympia Electronics - European manufacturer
TECHNICAL CHARACTERISTICS
(
for LED MODULE Specs. see page 6)
EBA
ΛΑ
+10gr
ΓΙΑ
ADDRESS