11 Connect the address cables, in the terminal block with the indicating polarity (Fig.2).
12 Address the luminaire by using the dip-switches with the appropriate combinations as you
can see in pages 4 and 5 (Fig.3).
Address module connections
Page
3 from
6
923039006_09_001
INDICATION LED STATUS (with the mains power supply connected
)
POWER / CHARGE
LAMP FAULT / BATT. FAULT
Disconnected battery
/
not charging
Normal operation mode
Charged battery
Low emergency duration
(
replace battery
)
Battery under charge
Lamp fault (Check lamps and replace if needed)
Indicator ON
Indicator Blinking
Indicator OFF
INSTALLATION PROCEDURE (For wall mounting only)
1
2
GR-6500 Loop
L
L
+L -L
1
1
L
L
Fig.2
Fig.3
Fig
.
1
Mounting holes
LAMP FAULT
BATT. FAULT
indicator
TEST
button
POWER
CHARGE
indicator
Cover
retaining
screws
1. Use the supplied mounting accessories to mount the device (fig1).
2. Remove the four cover retaining screws (fig 1).
3. Instal the battery cable connectors to the batteries taking care of the polarity, black cable (-) and red
cable (+).
4.
Always use in any case round mains cable, with external diameter of 6-9mm (H05RN-F type
2x1mm² or any other type, at least equal to it’s mechanical and electrical properties).
ATTENTION!! The cable must not be deformed in any way (This requirement is important to
ensure the tightness isolation IP 65).
Install
the cable gland, pass the round cable thru and tighten it all
the way.
5. Connect the cables to the respective positions in the terminal block
L for phase and N for neutral.
6. Reinstall the front cover and fasten the retaining screws. (Tightening torque 1Nm).
Pay attention to the 4
sealing o-rings.
WARNING!! After the installation has finished, charge the batteries for at least 24 hours so as to
obtain the rated autonomous duration
.
L
N