background image

STEP #1  

INSTALLING THE EMERGENCY BALLAST

                 > 

Disconnect AC power from the fixture. Remove the  

               

ballast channel cover and install the emergency 

 

               

ballast in the ballast channel (see Illustration 1).

 

       

  

       > 

Remote mounting distance must be less than half  

               

the maximum remote mounting distance for the  

         AC 

ballast. 

Consult 

AC 

ballast 

manufacturer 

 

         before 

remote 

installation.

STEP #2 

INSTALLING THE TEST SWITCH

                 > 

Refer to Illustration 2 and install the test switch  

               

through the ballast channel cover of a troffer or  

               

through the side of a strip fixture.

                 > 

Drill a 1/2" hole and install the switch as shown.  

                 > 

Wire the test switch so that it removes AC power  

               

from both the emergency ballast and the AC ballast  

               

at the same time (see Illustration 3).

STEP #3 

INSTALLING THE CHARGING 

  INDICATOR 

LIGHT

                 > 

Refer to Illustration 3A or 3B and install the charg- 

               

ing indicator light so that it will be visible after the  

               

fixture is installed.

WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON RED & YELLOW OUTPUT 

LEADS PRIOR TO INSTALLATION, INVERTER CONNECTOR MUST BE OPEN.  DO NOT JOIN 

INVERTER CONNECTOR UNTIL INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED 

TO THE EMERGENCY BALLAST.
NOTE:

  Make sure that the necessary branch circuit wiring is available. An unswitched 

source of power is required. The emergency ballast must be fed from the same 
branch circuit as the AC ballast.

ILLUSTRATION 1

ILLUSTRATION 2

INSTALLATION

UNSWITCHED FIXTURE

SWITCHED FIXTURE

UNSWITCHED FIXTURE

SWITCHED FIXTURE

SINGLE POLE

DOUBLE POLE OPTION

BLACK 120V

OR

ORANGE 277V

BLACK

AC

BALLAST

EMERGENCY 

BALLAST

WHITE

WHITE

HOT

COM

(CAP UNUSED LEAD)

SINGLE POLE

TEST SWITCH

(Breaking the Hot)

BLACK 120V

OR

ORANGE 277V

BLACK

EMERGENCY 

BALLAST

WHITE

WHITE

HOT

COM

(CAP UNUSED LEAD)

SINGLE POLE

TEST SWITCH

(Breaking the Common)

BLACK 120V

OR

ORANGE 277V

BLACK

EMERGENCY 

BALLAST

WHITE

WHITE

HOT

COM

(CAP UNUSED LEAD)

SINGLE POLE

TEST SWITCH

(Breaking the Hot)

BLACK 120V

OR

ORANGE 277V

BLACK

EMERGENCY 

BALLAST

WHITE

WHITE

HOT

COM

(CAP UNUSED LEAD)

SINGLE POLE

TEST SWITCH

(Breaking the Common)

WALL

SWITCH

WALL

SWITCH

AC

BALLAST

AC

BALLAST

AC

BALLAST

BLACK 120V

OR

ORANGE 277V

BLACK

AC

BALLAST

EMERGENCY 

BALLAST

WHITE

WHITE

BLK

HOT

COM

RED

RED

(CAP UNUSED LEAD)

BLK

WALL

SWITCH

BLACK 120V

OR

ORANGE 277V

BLACK

AC

BALLAST

EMERGENCY 

BALLAST

WHITE

WHITE

BLK

HOT

COM

RED

RED

(CAP UNUSED LEAD)

DOUBLE POLE

TEST SWITCH

BLK

DOUBLE POLE

TEST SWITCH

ILLUSTRATION 3

2

Fixture

Test Button

Hex Nut

Hex Nut

Test Switch

Leads

Push to Test

Summary of Contents for bodine LP400

Page 1: ...ectrical Code and any local regulations 4 To reduce the risk of electric shock disconnect both normal and emergency power supplies and inverter connector of the emergency ballast before servicing 5 This emergency ballast is for factory or field installation in the ballast channel or on top of fixture 6 This product is for use in indoor fixtures except air handling heated air outlets and wet damp o...

Page 2: ...E EMERGENCY BALLAST NOTE Make sure that the necessary branch circuit wiring is available An unswitched source of power is required The emergency ballast must be fed from the same branch circuit as the AC ballast ILLUSTRATION 1 ILLUSTRATION 2 INSTALLATION UNSWITCHED FIXTURE SWITCHED FIXTURE UNSWITCHED FIXTURE SWITCHED FIXTURE SINGLE POLE DOUBLE POLE OPTION BLACK 120V OR ORANGE 277V BLACK AC BALLAST...

Page 3: ...When power fails the emergency ballast automatically switches to emergency power operating one lamp at reduced illumination This emergency ballast will operate one 4 32 W T8 bipin lamp for a minimum of 90 minutes Although no routine maintenance is required to keep the emergency ballast functional it should be checked periodically to ensure that it is working The following schedule is recommended 1...

Page 4: ...M CHARGING INDICATOR LIGHT TO UNSWITCHED AC USE PROPER TAP CAP UNUSED LEAD EMERGENCY BALLAST LAMP 1 LAMP 2 LAMP 3 LAMP 4 EMERGENCY BLACK WHITE YELLOW YELLOW LINE RED RED BLUE BLUE WHT YELL BLK YELLOW RED AC BALLAST BLUE BLUE INVERTER CONNECTOR RED WHITE ORANGE BLACK WHITE VIOLET BROWN 277 V 120 V COM CHARGING INDICATOR LIGHT TO UNSWITCHED AC USE PROPER TAP CAP UNUSED LEAD EMERGENCY BALLAST LAMP 1 ...