INSTALLATION

Lumens In Emergency Mode = Lumens per Watt of Fixture * Output Power of Choosen Product
   ________________

(Lumens)

_ = __________________

(lm/W)

_* ____20  (W)__   _

2

NOTE:

  Make sure the necessary branch circuit wiring is available. An unswitched source of power is 

required. The emergency driver must be fed from the same branch circuit as the AC driver.

STEP #1

INSTALLING THE EMERGENCY DRIVER

>   Disconnect AC power from the LED luminaire.  

>  Mount the emergency LED driver by the mounting tabs using the supplied screws. The luminaire’s installation  

instructions may provide guidance on the recommended mounting location.  

>   The emergency driver may be remote mounted from the luminaire. If used in conjunction with an AC driver, this distance  

is up to half the distance the AC driver manufacturer recommends remote mounting the AC driver from the LED Load. If  

used without an AC driver, consult factory for remote mounting distances.

>  

Mounting Height:

 This product meets or exceeds the NFPA minimum light requirements with all loads, down to the 

smallest rated lamp load, at heights up to 7.17ft (2.2m). Many factors influence emergency illumination levels, such as 

the lamp load selected, luminare design, and environmental factors therefore end use verification is necessary. For field 

installations, when the attached luminaire is mounted at heights greater than 7.17ft (2.2m), the level of illumination 

must be measured in the end application to ensure the requirements of NFPA 101 and local codes are satisfied.

1. Ensure the LED load’s rated power is greater than or equal to the power output of this emergency LED driver. This is to  

  ensure that this emergency product will not produce more power than the LED load can handle, thus ensuring that the  

  LED load will not be damaged when the system is in the emergency mode.

 

2. Verify that the forward voltage of the luminaire’s LED array is within the limits of this emergency LED driver. The forward  

  voltage of the LED array is commonly designated as Vf and should be found on the luminaire markings, in the luminaire  

  specifications, or imprinted directly on the LED arrays. If multiple LED arrays are to be driven, verify that the total  

  forward voltage is within the limits of this product. Using a voltage meter, it may be possible to directly measure the  

  voltage across the LED arrays when operating from the AC driver.

 

3. Ensure the output current of the LED driver does not exceed 5.0 Amps. This is the current into the blue wire. 

4. Ensure there will be sufficient light output in the end application. Estimate the egress lighting illumination levels by  

  doing the following: 

      

    a.  Find the efficacy of the LED load. This can be given by the luminaire manufacture. This number will be given in   

      lumens per watt (lm/w). 

     b.  Lumens can be calculated by multiplying the output power of the emergency LED driver by the efficacy of the LED  

      load. In many cases the actual lumen output in emergency mode will be greater than this calculation gives, however  

      it will provide a good estimate for beginning the lighting design of the system. 

     C.  Using the results of this calculation and industry standard lighting design tools, calculate the anticipated  

 

      illumination levels in the path of egress.

 

This product is suitable for field installation with suitable LED loads including LED luminaires, DC voltage driven LED  

 

replacements for fluorescent lamps and others. There are 4 checks to determine if your luminaire is eligible for field  

 installation.

NOTE:

  This product has been designed to reliably interface with a wide selection of LED loads and is electrically compatible 

with every simple LED array that meets criteria 1 and 2 above. However, compatibility cannot be guaranteed with all current 

and future LED systems. Compatibility testing of the end-use system is suggested. Please contact the factory with any 

questions.

CAUTION: DO NOT JOIN CONVERTER CONNECTOR UNTIL INSTALLATION IS COMPLETE AND AC POWER IS 

SUPPLIED TO THE EMERGENCY DRIVER.

 

Installation of this emergency LED driver will vary based on the luminaire type, however, generally  

follow these steps:

NOTE:

 After installation, it will be necessary to measure the egress lighting illumination levels to ensure it complies with 

national, state, and local code requirements.

2

Summary of Contents for Bodine BSL20LV-DF

Page 1: ...plies and converter connector of the emergency driver before servicing 5 This emergency driver is suitable for both factory or field installation For field installation please see the instructions on page 2 6 This product is suitable for use in damp locations where the ambient temperature is 0ºC minimum 50ºC maximum Product is not suitable for heated air outlets and wet or hazardous locations Maxi...

Page 2: ...aire markings in the luminaire specifications or imprinted directly on the LED arrays If multiple LED arrays are to be driven verify that the total forward voltage is within the limits of this product Using a voltage meter it may be possible to directly measure the voltage across the LED arrays when operating from the AC driver 3 Ensure the output current of the LED driver does not exceed 5 0 Amps...

Page 3: ...tor light If the tube is too long cut the plastic tubing to necessary length After cutting the tube to the proper length assemble the 2W ITS To assemble the 2W ITS Assembly Feed the 2W ITS leads through the plastic tubing Insert the white bushing in the opposite end of tube from the 2W ITS body Pull switch leads and use provided tie wrap to secure leads snug against white bushing Unscrew hex nut t...

Page 4: ... indicator light is illuminated indicating that the battery is being charged When power fails the emergency LED driver automatically switches to emergency power internal battery operating the LED load for a minimum of 90 minutes When AC power is restored the emergency driver returns to the charging mode Although no routine maintenance is required to keep the emergency driver functional it should b...

Reviews: