background image

ActiLume Classic 

LRM2310 

LRM2315 
LRM2320 
LRM2325 

 

Installation and 
Programming Guide 

Field of View 

LRM2310 / 2315 High Bay 360° Lens  

Recommended for fixtures that have a 
1:1 spacing to mounting height ratio or 

less (e.g. fixtures 30’ on center or less 
@ a 30’ mounting height). 

 

Recommended for mounting heights 
between 30 to 40 ft (9.14 to 12.2 m) 
only  

15 to 20 ft (4.57 to 6.1 m) radial 
coverage overlaps area lit by a typical 
high bay fixture  

Excellent detection of large motion 
(e.g. walking) up to a 40 ft (12.2 m) 

mounting height  

Parts of the sensor carry line power, which is 

a potential lethal voltage. This product was 

designed and manufactured to ensure 

maximum safety during operation and 

service.  Always read these safety instructions 

before installing, maintaining or servicing the 

product, and strictly comply with these 

instructions. 

- This product should be installed by a 

qualified electrician. 

- This device is designed for indoor use only.  

- Disconnect power at circuit breaker or fuse 

when servicing, installing or removing. 

- Only use with copper or copper clad wire. 

- Wire sensor to the line power according to 

the wiring scheme in this guide.  

- To avoid short circuits, do not expose this 

product to rain or condensing moisture.  

Short circuit may cause fire or electric shock 

hazard.  Operate the devices between 14°F 

to 160°F (-10°C to 71°C) ambient 

temperature. . 

It is the installer’s responsibility to ensure that the 
equipment being controlled is visible from every 

control location and that only suitable equipment is 
connected to these controls. Failure to do so could 
result in serious injury or death. 
 
The product is intended to control lighting loads.  Do 
NOT use to control equipment that could create 

hazardous situations, like entrapment.  For examples, 
do NOT install this product to control motorized 
gates, garage doors, industrial doors, microwave 
ovens, heating devices, etc.  

Warning 

Important Safety Information 

- Whenever it is suspected that an unsafe 

condition exists, switch off power at the 

circuit breaker and replace the device.  Safety 

is likely to be impaired if, for example, the 

equipment fails to perform the intended 

functions or if the equipment shows visible 

damage.  Do not paint the device. 

- Use only a soft damp cloth to clean, never 

use any abrasive or chemical cleaner. 

Product Description 

ActiLume Classic Snap-In occupancy sensor is 

a compact line voltage sensor that snaps 

directly into a small cavity in a fixture. The 

sensor utilizes Passive Infrared (PIR) detection 

to detect motion from occupants within its 

360º coverage pattern. 

The sensor detects changes in the infrared 

energy given off by occupants as they move 

within the field-of-view. When occupancy is 

detected, a self-contained relay switches the 

lighting ON. The sensor is line powered and 

can switch a large range of line voltages. An 

internal timer, factory set at 15 minutes, 

keeps the lights on during brief periods of no 

activity. This timer is push-button 

programmable from 30 seconds to 20 

minutes, and is reset every time occupancy is 

re-detected. This state-of-the-art design 

requires no manual sensitivity adjustments. 

The LampMinder minimum On time feature 

preserves lamp life by eliminating all lamp 

cycles shorter than lamp manufacturers’ 

recommendations. 

20                     0 ft                     20

6.1

                    

0 m

                    

6.1

SIDE VIEW

0 ft

10

20

30

40

0 m

3

6.1

9.1

12.2

20

10

0 ft

10

20

6.1

3

0 m

3

6.1

TOP VIEW

LRM2320 / 2325 Low Bay 360° Lens  

Recommended for walking motion detection from mounting heights between 8 ft (2.44 m) 
and 20 ft (6.10 m)  

Initial detection of walking motion along sensor axes at distances of 2x the mounting 
height up to 15 ft (4.57 m) and 1.75x up to 20 ft (6.10 m).  

Provides 12 ft (3.66 m) radial detection of small motion when mounted at 9 ft (2.74 m)   
Initial detection will occur earlier when walking across sensor’s field of view than when 
walking directly at sensor  

9 ft Mounting 

15 ft Mounting 

Wiring 

Initial Turn ON for all models 

Turn OFF breaker all circuits involved. Wiring the 
device with power ON could result in serious injury 

or death. 

Danger 

LRM2310 / 2315 / 2320 / 2325 Wiring 

BLACK* - Line Input  

BLACK* - Load Output  

WHITE - Neutral 

347 VAC Models LRM2315 / 2325 

Black wires are replaced w/ Red wires  

The sensor’s relays are shipped in a latched 
closed position so the lights will come on 
upon initial power-up. If the lights do not 
immediately turn on (initial installation only) 
the latching relays opened during shipment 
and will close within 30 seconds.  

Note: If the sensor loses power, the relays 
will latch to ON.  

* Black wires can be reversed 

Mounting 

The snap fit enclosure is designed to fit 
snuggly inside a 2 3/16” H x 1 5/16” W x 
1” D cavity in a lighting fixture.  
For optimal detection, position sensor 
such that a long coverage segment is 
aligned with aisle way or entrance. Long 
segments are aligned with the sensor axes 
and at all 30° offsets from the axes.  

Diagrams show internal cross section of 
fixture with bracket included for 
additional sensor impact strength.  

Lens Masking 

A lens masking kit is provided in order to 

mask off a portion of the view pattern for 

end-of-aisle applications; or to trim the 

sensor’s side viewing to create a rectangular 

pattern for center-of-aisle viewing only.  

Input Voltage: 

120-277 VAC (LRM2310, LRM2320); 

347VAC (LRM2315, LRM2325) 

Operational Frequencies: 

50/60Hz (Timers are 1.2x for 50Hz) 

Load Rating (1 Phase only): 

800W @ 120VAC; 1200W @ 277VAC; 

1500W @ 347VAC; Motor Load: 1/4 HP  

Operating Environment: 

14 to 160°F (-10 to 71°C) 

20% to 90% non-condensing, relative 

humidity. For indoor use only.  

Size: 

2.25"H x 1.38"W x 0.82"D  

Weight: 

4 oz 

Specifications 

Reviews: