background image

Function Definitions 

2 Occupancy Time Delay 

The length of time an occupancy sensor will 

keep the lights on and at full bright after it last 

detects occupancy (assuming minimum on 

time has been met) 

4 100 Hour Burn-In / Test Mode 

Disables Minimum On Time, sets Occupancy 

Time Delay to 30 sec, and shortens all 

photocell transition and dimming rates. Mode 

will expire after 10 min or if function 4 is set 

back to Normal. 

100 Hour Burn-In  

Overrides relay on and/or dimming output 

to full bright (typically for lamp seasoning) 

Test Mode 

Disables Minimum On Time and sets 

Occupancy Time Delay to 30 sec. Mode 

will expire after 10 min or if function 4 is 

set back to Normal. 

10 Minimum On Time 

The length of time required for lamps to be 

on in order to prevent all short cycling that 

shortens lamp life. If occupancy time delay 

expires prior to minimum on time being 

satisfied, the lamps will remain on until time 

has been met.  

 

Programming 

Please read all 3 steps before programming 

1. Enter a programming function by pressing 

button, on front of device, the number of 

times as the desired function number from 

the tables below (e.g., press twice for 

function 2, occupancy time delay). 

2. LED will flash back the selected function's 

current setting (e.g., 5 flashes for 10 minute 

time delay). To change setting, proceed to 

step 3 before flash back sequence repeats 3 

times. To exit the current function or to 

change to a different function, wait for 

sequence to repeat 3 times then return to 

step 1. 

3. Press button the number of times 

indicated in the particular function's detailed 

table for the NEW desired setting (e.g., press 

3 times for 5 min). As confirmation of setting 

change, LED flashes back the NEW setting 3 

times before exiting. 

Function 

Description 

Occupancy Time Delay 

Test Mode & 100 hr Burn-In 

10 

Minimum On Time 

Programming Functons 

2 Occupancy Time Delay 

Selection 

Time 

30 sec 

2.5 min 

5 min 

7.5 min 

10 min* 

12.5 min 

15 min 

17.5 min 

20 min 

* default setting 

10 Minimum On Time 

Selection 

Time 

0 min 

15 min* 

30 min 

45 min 

60 min 

* default setting 

The Philips ActiLume products, when properly installed and under normal conditions of use (without overload, 

abuse or alteration), is warranted to you, the original user, for a period of two (2) years from the date of original 

purchase, to be free from defects in materials and workmanship. If during the warranty period you believe the 

purchased product or any part thereof has such a defect, you must return the product (or part) at your cost 

during such period, with proof of purchase (or if installed by a third party a written explanation of installation 

transaction with proof of date), to Philips Lighting Electronics N.A (1-800-372-3331 / www.philips.com/advance), 

for repair or replacement (or to an authorized Philips Lighting Electronics N.A. supplier which agrees in advance to 

handle the return and replacement by factory authorization). If the product or part is found by Philips to have 

been defective in material or workmanship it will be repaired or replaced (as deemed necessary by Philips Lighting 

Electronics N.A.), and the replacement will be returned to you free of charge. The original user is solely 

responsible for any costs associated with removal and re-installation of the product and shipping to Philips Lighting 

Electronics N.A. or its authorized supplier. 

 

Warranty Statement 

Contact Information 

©2011 Philips Lighting Electronics North America. 
A Division of Philips Electronics North America Corporation. 
 
All rights reserved. 
Printed in the USA 

Published 10/1 
Part No. LRM2310-INSTALL-B

Philips Lighting 
10275 West Higgins Road 
Rosemont, IL 60018 
Customer Care/Technical Service: 800-372-3331 
Email: [email protected] 
Website: www.philips.com 
 

Selection 

Operation 

Normal* 

Run 100 hr Burn-In 

Test Mode

4 Test Mode / 100 hr Burn-In 

1

 Test Mode will disable Minimum On Time, 

set Occupancy Time Delay to 30 sec. Mode 

will expire after 10 min or if function 4 is set 

back to Normal. 

* default setting 

Reviews: