Important Note:
If the connected load requires a wye configured power source with a neutral connection,
the load must be connected to the phase converter using a delta-wye isolation transformer.
Figure 6
– Delta Wye Wiring Diagram
Table 9 Input Power Terminal Specifications
Input Power Terminals: Allowed Wire Range & Minimum Torque
Model
PT007, PT010, PT020,
PT407, PT410, PT415,
PT420, PT430, PT440,
PT450
PT030, PT040, PT460,
PT475
PT050, PT060, PT075,
PT4100
Wire Size
Torque
Wire Size
Torque
Wire Size
Torque
2/0
– 6 AWG
120 in-lb
350 kcmil-
6 AWG
275 in-lb
2x500 kcmil-
2x4 AWG
375 in-lb
8 AWG
40 in-lb
10
– 14 AWG
35 in-lb
Table 10 Output Power Terminal Specifications
Output Power Terminals: Allowed Wire Range & Minimum Torque
Model
PT007, PT010, PT020, PT030, PT040,
PT407, PT410, PT415, PT420, PT430,
PT440, PT450, PT460, PT475, PT4100
PT050, PT060, PT075
Wire Size
Torque
Wire Size
Torque
2/0
– 6 AWG
120 in-lb
350 kcmil
– 6 AWG
275 in-lb
8 AWG
40 in-lb
10
– 14 AWG
35 in-lb