4. Technical data
4.1. Application limits
4.1.1. Ambient temperature limitation
Chiller is designed to operate in the ambient temperature range indicated on the type label. When ambient
temperatures are out of that range, manufacturer must be consulted.
4.1.2. Voltage limitations
According to CEI EN 60204-1, Pfannenberg standard chiller operation is guaranteed within these ranges:
• Nominal voltage ±10 %
[V]
• Nominal frequency ±1 %
[Hz]
Please refer to the type label to see the nominal operating conditions of the unit.
Nominal conditions
V min [V]
V max [V]
f min [Hz]
f max [Hz]
230 V / 1 ~ / 50 Hz
207
253
49.5
50.5
230 V / 1 ~ / 60 Hz
207
253
59.4
60.6
400 V / 3 ~ / 50 Hz
360
440
49.5
50.5
460 V / 3 ~ / 60 Hz
414
506
59.4
60.6
NOTICE
Special voltage
For units with special voltages please refer to the type label.
4.2. Type label
This is an example of a type label.
Important is the information of the chiller serial number, which is needed for all technical questions.