13. TECHNICAL SPECIFICATIONS
13.1 FEATURES
The accuracy is stated as [1% of the reading ± number of 2 digits]. It refers to the
following atmospheric conditions: temperature 73°F± 2°F (23°C ± 1°C) with rela-
tive humidity < 75%.
41
DM-4 Power Quality Recorder
13.1.1 Voltage Measurement
Range
Accuracy
Resolution
Input Impedance
20-370V
±(3%+2digit)
0.1V
300kΩ (phase-neutral)
310-635V
0.1V
600kΩ (phase-phase)
13.1.2 Voltage Anomalies Detection (Manual Selection of Range) Voltage
Range
Accuracy
Resolution
Input Impedance
20-370V
±(3%+2digit)
0.1V
300kΩ (phase-neutral)
310-635V
0.1V
600kΩ (phase-phase)
Time
Accuracy (ref. to 60Hz)
Resolution
±8.33ms (
1/2
period of fundamental) 8.33ms (
1/2
period of fundamental)
13.1.3 Current Measurement (Using external transducer)
Range
Accuracy Resolution
Input
Impedance
Protection against
overloads
0.005-0.26V ±(2%+2digit)
100kΩ
5V
0.26-1V
Minimal Current measurable is equal to 0.5% of Clamp Full Scale