VersiStart i II
9
Soft Stop Time
08248.
A
Select the soft stop ramp time (D).
Soft stop extends the time soft starter takes to
reduce voltage to zero.
The ramp time does not control the time the motor
will take to stop completely.
Volt
ag
e
Time
Excess Start Time
08249.
A
Configure the soft starter's excess start time
protection.
Select a time slightly longer than the motor requires
for a normal healthy start. The soft starter will trip if
the start does not complete within the selected time
(E).
Cu
rren
t
Time
Auxiliary Relay Function
08250.
A
Select the function of the soft starter's
programmable output (terminals 23, 24).
When set to "Run", the relay will operate when the
soft start is complete. When set to "Trip", the relay
will operate when the soft starter trips.
Time
Phase Sequence Protection
08251.
A
Configure the soft starter's phase sequence
protection.
Select the allowable phase sequences. A setting
of "Fwd" allows forward sequence (positive
rotation) only and a setting of "Any" defeats the
protection.
NOTE
Auxiliary relay function and phase sequence are configured using a shared switch. Set the auxiliary
relay function as required, then set phase sequence protection.