14
VersiStart i II
EMC Immunity
Electrostatic discharge ................................................................... 4 kV contact discharge, 8 kV air discharge
Radio frequency electromagnetic field .................................................... 0.15 MHz to 1000 MHz: 140 dB (µV)
Rated impulse withstand voltage (Fast transients 5/50 ns) .......................... 2 kV line to earth, 1 kV line to line
Voltage dip and short time interruption ........................................................... 100 ms (at 40% nominal voltage)
Harmonics and distortion .................................................................... IEC61000-2-4 (Class 3), EN/IEC61800-3
Short Circuit
Rated short-circuit current VS i II 018 to VS i II 048 .................................................................................. 5 kA
1
Rated short-circuit current VS i II 060 to VS i II 200 ................................................................................ 10 kA
1
1
These short circuit ratings are with fuses used as given in the table under Semiconductor Fuses on page 16.
Heat Dissipation
During Start ............................................................................................................................. 3 watts / ampere
During Run ................................................................................................................................ 10 watts typical
Standards Approvals
CE ............................................................................................................................................. EN 60947-4-2
Lloyds ........................................................................................................................................ IEC 60947-4-2
UL / C-UL ................................................................................................................................................. UL 508
Operational Life
VS i II 018~100 ............................................................................................................... 1,000,000 operations
VS i II 140~200 .................................................................................................................... 30,000 operations