VersiStart i II
5
4.
Electrical Installation
4.1
Power Terminations
L1/1, L2/3, L3/5, T1/2, T2/4, T3/6
mm
2
(AWG)
A1, A2, A3, 01, 02,
B4, B5, 13, 14, 23, 24
mm
2
(AWG)
018 - 060
075 - 100
140 - 200
018 - 200
1
0
4
2
7
.A
10 - 35
(8 - 2)
1
0
4
2
8
.A
14 mm
(0.55
inch)
25 - 50
(4 - 1/10)
1
0
4
2
8
.A
14 mm
(0.55
inch)
n/a
26
(1.02)
11
(0.43)
Ø 8.5
(0.33)
1
0
4
2
9
.A
mm (inch)
0.14 - 1.5
(26 - 16)
1
0
4
2
8
.A
6 mm
(0.24
inch)
Torx (T20)
3 Nm
2.2 ft-lb
Torx (T20)
4 Nm
2.9 ft-lb
n/a
n/a
7 mm
3 Nm
2.2 ft-lb
7 mm
4 Nm
2.9 ft-lb
n/a
3.5 mm
0.5 Nm max
4.4 in-lb max
4.2
Control Voltages
VersiStart i II soft starters can be supplied in either of two control voltage configurations:
VS i II xxx xxx C1 .... 110-240 VAC (+ 10% / - 15%) or 380-440 VAC (+ 10% / - 15%)
VS i II xxx xxx C2 .... 24 VAC/VDC (± 20%)
WARNING
Always apply control voltage before (or with) mains voltage.
CAUTION
With 24 VAC/VDC use contacts rated for low voltage and low current (gold flash or similar).