8   OPERATE

Parameters

Standard Parameters

Par.

Description

Min

Max

Default

Units

P-01

Maximum Frequency/Speed Limit

P-02

500.0

50.0 (60.0)

Hz/RPM

P-02

Minimum Frequency/Speed Limit

0.0

P-01

0.0

Hz/RPM

P-03

Acceleration Ramp Time

0.00

600.0

5.0

s

P-04

Deceleration Ramp Time

0.00

600.0

5.0

s

P-05

Stopping Mode/Mains Loss Response

0

4

0

-

Setting

On Disable

On Mains Loss

0

Ramp to Stop (P-04)

Ride Through (Recover energy from load to maintain operation)

1

Coast

Coast

2

Ramp to Stop (P-04)

Fast Ramp to Stop (P-24), Coast if P-24 = 0

3

Ramp to Stop (P-04) with AC Flux Braking

Fast Ramp to Stop (P-24), Coast if P-24 = 0

4

Ramp to Stop (P-04)

No action

P-07

Motor Rated Voltage/Back EMF at rated speed (PM/BLDC)

0

250/ 500

230/400

V

P-08

Motor Rated Current

Drive Rating Dependent

A

P-09

Motor Rated Frequency

10

500

50 (60)

Hz

P-10

Motor Rated Speed

0

30000

0

RPM

P-11

Low Frequency Torque Boost

0.0

Drive Dependent

%

P-12

Primary Command Source

0

9

0

-

0: Terminal Control
1: Uni-directional Keypad Control
2: Bi-directional Keypad Control
3: Modbus Network Control
4: Modbus Network Control

5: PI Control
6: PI Analog Summation Control
7: CAN Control
8: CAN Control
9: Slave Mode

NOTE

 When P-12 = 1, 2, 3, 4, 7, 8 or 9, an enable signal must still be provided at the control terminals, digital input 1.

P-14

Extended Menu Access code

0

65535

0

-

Extended Parameters

Par.

Description

Min

Max

Default

Units

P-15

Digital Input Function Select

0

17

0

-

P-16

Analog Input 1 Signal Format

See Below

U0-10

-

8

 : Unidirectional, External 0 – 10Volt reference / pot

%

 : Bi-directional, External 0 – 10Volt reference / pot

$

 : External 0 – 20mA signal

W

 : External 4-20mA signal, trip on loss

U

 : External 4 – 20mA signal

W

 : External 20 – 4mA signal, trip on loss

U

 : External 20 – 4mA signal

8

 : External 10 – 0 Volt signal

,QSRW

 : 

Switched units only

 : Internal pot

P-18

Output Relay Function Select

0

9

1

-

0: Drive Enabled (Running)
1: Drive Healthy
2: At Target Frequency (Speed)
3: Drive Tripped
4: Output Frequency >= Limit

5: Output Current >= Limit 
6: Output Frequency < Limit
7: Output Current < Limit
8: Analog Input 2 > Limit
9: Drive Ready to Run

P-20

Preset Frequency / Speed 1

-P-01

P-01

5.0

Hz/RPM

P-21

Preset Frequency / Speed 2

-P-01

P-01

25.0

Hz/RPM

P-22

Preset Frequency / Speed 3

-P-01

P-01

40.0

Hz/RPM

Summary of Contents for VDI-037-3E3-IP66

Page 1: ...e l e c t r o n i c AC Converter VersiDrive i E3S IP66ODS Quick Start Manual Quality is our drive...

Page 2: ...ersiDrive must be mounted in a vertical position only Installation should be on a suitable at ame resistant surface Do not mount ammable material close to the drive Refer to Technical Data and ensure...

Page 3: ...ve Below Y Either Side mm in mm in All Frame Sizes 200 7 87 10 0 39 NOTE Typical drive heat losses are approximately 3 of operating load conditions Above are guidelines only and the operating ambient...

Page 4: ...egulations Maximum dimensions are given in the Rating Tables section of this Quick Start Guide Install the Wiring L1 L L3 EMC Gland plate can be removed for installation L2 N U V W 1 2 3 4 5 6 7 8 9 1...

Page 5: ...he line side of this equipment and shall be rated 480Volt phase to ground 480 Volt phase to phase suitable for over voltage category iii and shall provide protection for a rated impulse withstand volt...

Page 6: ...ed set P 16 to the correct format NOTE Additional functions are possible refer to the online documentation for further information Motor Thermistor Connection Where a motor thermistor is to be used it...

Page 7: ...econd The display will show the motor power kW If P 10 0 pressing the Navigate key for 1 second will display the motor speed RPM Changing Parameters 67R3 3 3 3 3 Press and hold the Navigate key 2 seco...

Page 8: ...al Keypad Control 3 Modbus Network Control 4 Modbus Network Control 5 PI Control 6 PI Analog Summation Control 7 CAN Control 8 CAN Control 9 Slave Mode NOTE When P 12 1 2 3 4 7 8 or 9 an enable signal...

Page 9: ...ly Closed operation is supported depending on Index 2 setting The drive will remain in Fire Mode until disabled or powered off P 31 Keypad Start Mode Select 0 7 1 0 Minimum Speed Keypad Start 1 Previo...

Page 10: ...owing procedure can be used 1 The motor must be correctly connected to the drive and safe to operate before using this procedure 2 Ensure the motor rated voltage P 07 and current P 08 have been correc...

Page 11: ...Maximum Cable Size Output Current Recommended Brake Resistance Non UL UL mm AWG A 110 115 10 V 1 Phase Input 3 Phase Output 1 0 37 0 5 8 5 16 15 8 8 7 0 2 0 75 1 12 5 16 15 8 8 10 5 100 200 240 10 V 1...

Page 12: ...13 DC bus ripple too high 3 266 14 Input phase loss trip K 2 15 Output Over Current WK OW 16 Faulty thermistor on heatsink G W 17 Internal memory fault IO 18 4 20mA Signal Lost G W 19 Internal memory...

Page 13: ...Phone 49 0 9189 4147 0 Fax 49 0 9189 4147 47 eMail mail peter electronic com PETER electronic GmbH Co KG Bruck cker 9 D 92348 Berg www peter electronic com...

Reviews: