15
5.1.3
ANALOG INPUT/OUTPUT
The pump has three analog inputs/outputs with different functions. They can be configured through the web
interface (page “pump”) or through Modbus.
5.1.4
RELAY OUTPUT
5.1.5
ETHERNET
The pump has a built in web server which allows you to access your pump directly via an existing Ethernet
connection. The default address for access to the pump is "perfectapro" or 192.168.0.245
The web server uses HTML pages to set/view:
Regulation mode settings
Regulation parameters (power, RPM, head, flow)
Relay settings
External control inputs settings
Current and previews error
Pump statistics (power consumption, run time and other)
5.1.6
MODBUS
Pump has built in Modbus client, through which we can access pump information using the RS 485 standard.
Modbus allows to set and view:
Regulation mode settings,
Regulation parameters (power, RPM, head, flow),
Relay settings,
External control inputs settings,
Current and previews error,
Pump statistics (power consumption, run time and other).
Input/Output
Function
Function description
SET1
Run [Default - Mode 1]
Turning the pump on/off. By default activating with connection to
SET3.
SET2
Max/Min [Default - Mode 1]
Set the pump to max. settings when SET1 is active and to min.
settings when SET1 is inactive.
SET3
FB [Default - Mode 1]
10 V voltage output used for activating SET 1 and SET2 by
connecting them to SET3.
Configuration
Description
Run
Shows when pump is running.
Operate
Shows when pump is standby.
Error[Default]
Shows when pump has an error.
No function
Relay output doesn’t show anything.
Always on
Relay always closed.