background image

12

 STEP 3:

PREPARE AND INSTALL CABINET

1.  Slide chassis from cabinet. Refer back to Step 1 of 

Window Mounting section.

2.  Place cabinet into opening with bottom rail resting 

firmly on bottom board of wooden frame.

3.  Position cabinet to achieve proper slope for water 

removal. (See Fig. 5.)

4.  Secure bottom rail to wooden frame with two large 

wood screws 1″ (2.5 cm) long using the two holes in 

the bottom of the channel resting on frame. (See  

Fig. 6.)

Refer to Step 5 of Window Mounting section for 

assembly of support brackets. A wooden strip nailed to 

the outside wall should be used in conjunction with sill 

support angle brackets. (See Fig. 7.)
5.  Screw or nail cabinet wooden frame using shims, if 

frame is oversized, to eliminate distortion. (See Fig. 

8.) Remember to maintain proper slope, as described 

in Step 3.

6.  Install chassis into cabinet by following all directions 

in Step 9 of Window Mounting section.

OPTIONAL:

 Caulking and installation of trim on interior 

wall may be done. You can buy wood from your local 

lumber or hardware supply. On the outside, caulk 

openings around top and sides of cabinet, and all sides 

of wood sleeve to the opening.

NOTE: 

See Fig. 11 of Window Mounting Instructions for 

bottom rail seal location.

NOTE:

 Check that air 

conditioner is tilted back 

about 1-1/2

 to 1-5/8

 

(3

°

 to 4

°

 downward 

toward the outside). If, 

after proper installation, 

condensation does not 

drain from the overflow 

drain hole during normal 

use, adjust slope.

MASONRY CONSTRUCTION

1.  Cut or build a wall opening in the masonry wall 

similar to the frame construction (refer to Step 2 of 

Thru-The-Wall Installation for wall thickness greater 

than 8

½

″).

2.  Secure cabinet in place using masonry nails or the 

right masonry anchor screws. (Another way to do this 

is to build an in-between frame of 2x4’s as shown 

in step 2 of Thru-The-Wall Installation but make it 

double framed on either side and install between 

masonry wall opening and cabinet. Frame must be 

securely anchored to masonry wall opening.) This 

way gives very good louver clearance on either side 

of the cabinet.

3.  Install a lintel to support masonry wall above 

cabinet. Existing holes in cabinet can be used and/

or additional holes can be drilled to fasten cabinet 

at various positions. Be sure that side louver 

clearance is in accordance with Step 1 of Masonry 

Construction.

4.  Install exterior cabinet support brackets as shown in 

Step 3 of Thru-The-Wall Installation. Caulk or flash 

if needed to provide a weather-tight seal around top 

and sides of cabinet.

5.  To complete installation, apply wood trim molding 

around room side projection of cabinet.

NOTE: After installing, make sure the air conditioner is 

tilted 3-4° to the outside to allow water drainage and 

perfect cooling efficiency.

 

 

FIG. 5

FIG. 7

FIG. 8

FIG. 6

3 ~ 4

°

Side Louvers

1

 Long Wood Screw

Sill angle bracket

Wooden Strip

Support 

bracket

Summary of Contents for 4PAC15000

Page 1: ...WINDOW AIR CONDITIONER FOR MODEL 4PAC15000 4PAC18000 4PAC25000 Before using your air conditioner please read this manual carefully and keep it for future reference along with your receipt USER MANUAL...

Page 2: ...___________________________ Purchase Date _____________________________________ Store Purchased ______________________________________ Installation Date ____________________________________ Installati...

Page 3: ...ir or maintenance of this unit If necessary contact an installer for installation of this unit The air conditioner is not intended for use by young children without supervision Young children should b...

Page 4: ...the unit Failure to do so may cause fire and electric shock DO NOT use the socket if it is loose or damaged Doing so may cause fire and electric shock DO NOT open the unit during operation Doing so m...

Page 5: ...d of time unplug or turn OFF main power switch Leaving power on may cause unit failure or fire Do not place obstacles around air inlets or inside of air outlet Obstacles may cause appliance failure or...

Page 6: ...sure the air conditioner has been securely and correctly installed according to the installation instructions in this manual Save this manual for possible future use in removing or installing this un...

Page 7: ...Do not under any circumstances cut or remove the third ground prong from the power cord Do not change the plug on the power cord of the air conditioner Aluminum house wiring may present special proble...

Page 8: ...or 31 Max Window Width 401 2 or 42 1 CHECK WINDOW OPENING SIZE The mounting parts furnished with this air conditioner are made to install in a wooden sill double hung window The standard parts are for...

Page 9: ...ing screws from top of unit See Fig 5 8 Hold the cabinet while pulling on the base handle and carefully remove the unit 9 Add two foam inserts to holes in top of cabinet where shipping screws were rem...

Page 10: ...panel frame into channel in the top angle and bottom rail Do this on both sides 4 Insert washer head locking 7 16 screws 2 into holes in top leg of filler panel frame See step 6 on next page Do not to...

Page 11: ...adjust slope Fig 14 FIG 14 FIG 15A Mark About 11 2 to 15 8 Window Sash Side Louvers Sill Angle Bracket Window Sill Measure from the cabinet edge 5 FIG 15B Right Left Locknut 1 2 Log Screws and Locknut...

Page 12: ...ne 3 4 or 1 2 long hex head screw A 3 4 or 1 2 long hex head screw B Left hand Window Filler Panel Top Leg C Window channel A 3 4 or 1 2 long hex head screw A A B C Window Sash Weather Seals FIG 18A F...

Page 13: ...width in Step 10 1 Cut the insulation panel along the line Fig 21 or STEP 10 3 Slide the insulation panel you just cut into the accordion panel curtain The side of the insulation panel with the patte...

Page 14: ...ill be installed by sounding wall or by magnetically finding nails 2 Cut or knock out a hole on each side of center stud 3 Measure between inside edges of every other stud as shown in Fig 1 NOTE Caref...

Page 15: ...de If after proper installation condensation does not drain from the overflow drain hole during normal use adjust slope MASONRY CONSTRUCTION 1 Cut or build a wall opening in the masonry wall similar t...

Page 16: ...all of its functions Afterwards follow the symbol for the functions you desire BEFORE operating the unit This unit can be controlled by the unit control or the remote control Remote Signal Receptor TO...

Page 17: ...m AUTO COOL DRY HEAT for units with heating function and FAN The indicator light will be illuminated and remain on once the mode is selected The unit will automatically initiate the Energy Saver funct...

Page 18: ...rection is obtained Move the levers from side to side until the desired Left Right direction is obtained ADDITIONAL THINGS YOU SHOULD KNOW The Cool circuit has an automatic 3 minute time delayed start...

Page 19: ...m the filter clean NOTE Never use hot water over 104 F 40 C to clean the air filter Never attempt to operate the unit without the air filter CABINET CLEANING Be sure to unplug the air conditioner to p...

Page 20: ...he coil set to FAN only mode Then set temperature to a higher setting AIR CONDITIONER CYCLING ON AND OFF TOO FREQUENTLY OR NOT ENOUGH Be sure unit is not too large or too small for the area of the roo...

Page 21: ......

Page 22: ......

Page 23: ...The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details...

Page 24: ...Line Rd Suite 878 Dallas TX 75254 Distributed by 844 4PA AIRE 844 472 2473 www perfectaire us Specification and performance data is subject to change without notice Printed in China PA User4PAC15000_4...

Reviews: