2
0
1
7
-0
5
40
Configuration
Identification Parameters
Parameter
Description
Default
Long Tag
Identifies the device in a
Wireless
HART network. Enter up to
32 characters.
–
Device Tag
Identifies the field device within the process plant. Enter up to
8 characters.
–
Descriptor
Further description of the device. Enter up to 16 characters.
–
Date Code
Date of last parameter change. Format: DD.MM.YYYY
01.04.2009
Message
User defined message. Enter up to 32 characters.
–
Polling
Address
HART address of the adapter on the wired interface, valid
range 0 ... 63. Since the long tag and MAC address are used
to identify the device in the
Wireless
HART network, it is not
necessary to give different devices different polling
addresses.
15
Country Code
Select the country code of the country in which the device is
operated from this drop-down list.
■
Governs the signal strength that can be set for the device
■
Determines the preset value for "SI Units only"
–
SI Units only
Selects the unit set to be used by the adapter.
■
Unit codes restricted to SI units only: only SI units are
displayed
■
No restrictions: Both metric and US units are displayed