![Pepperl+Fuchs WCS DG310 Manual Download Page 9](http://html1.mh-extra.com/html/pepperl-fuchs/wcs-dg310/wcs-dg310_manual_1527703009.webp)
Commissioning
2
0
1
7
-1
2
9
4
Commissioning
4.1
Meaning of LEDs
Power:
The "Power" LED is green: The WCS-DG310 interface module is correctly connected to the
power supply.
BusPower:
The "Power" LED is green: The LED is connected directly to the electrically isolated supply
voltage of the DeviceNet side.
BusState:
State:
The "State" LED is green: Data exchange is taking place with the WCS readers. Using the 4
"Error No/Select ID" LEDS, the number of the currently polled WCS reader is displayed.
The "State" LED is red: The interface module has detected an error or a warning. The interface
module displays the binary coded error and/or warning number via the "Error No/Select ID"
LEDs.
“
BusState" LED
DeviceNet interface state
Lights up green
Connected to the DeviceNet master
Flashes green
No connection to the DeviceNet master
Lights up red
Serious error on DeviceNet bus (for example, duplicate MAC ID)
Flashes red
Recoverable error (e.g., timeout error)
Flashes red/green
Communication errors
Table 4.1
"BusState" LED display
ErrorNo/Select ID
Reader address
8
4
2
1
0
0
0
1
0
0
0
1
0
1
0
1
0
0
2
1
0
0
0
3
Table 4.2
Display of the 4 LEDs "Error No/Select ID" when the "State" LED lights up green
Error (No. 1...5):
Switch the interface module off and back on. If the error occurs
again, the module must be replaced.
Warning (No. 6...15):
The warning provides information. The interface module displays
the warning for one minute and then resets automatically.