Pepperl+Fuchs WCS DG310 Manual Download Page 14

 2

0

1

7

-1

2

14

WCS DG310

Commissioning

Bit-strobe

With bit-strobe access, the "Bit-strobe" command is sent from the master without any further 
data. The master then always receives 8 data bytes from the interface module as a response. 
The 8 data bytes contain the data of the WCS readers with the address 0 and 1 (2 x 4 bytes). If 
the WCS reader with address 1 is not connected (rotary switch S4 is in position 1), the 4 data 
bytes for this WCS reader are 0x00.

Change of state

In this method, the WCS-DG310 sends 8 data bytes to the master without request as soon as 
the content of the data has changed. The data format corresponds to the data format for bit-
strobe access. If the WCS reader data changes constantly, e.g., if the reader is moving quickly, 
the data is sent every 5 ms. In this case, the pause time is necessary to avoid overloading the 
DeviceNet bus.

Interface module data format for one WCS reader

4.7

EDS configuration file

To assist with the configuration, you can download the EDS file from the download area of our 
Internet homepage http://www.pepperl-fuchs.com. Simply enter the product name or item 
number in the 

Product/Keyword

 search box and click 

Search

.

Select your product from the list of search results. Click on the information you require in the 
product information list, e.g., 

Software

.

A list of all available downloads is displayed.

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Word n

0

0

0

0

0

P

1

8

P

1

7

P

1

6

P

1

5

P

1

4

P

1

3

P

1

2

P

1

1

P

1

0

P

0

9

P

0

8

Word n+1

P

0

7

P

0

6

P

0

5

P

0

4

P

0

3

P

0

2

P

0

1

P

0

0

0

0

0

D

B

E

R

R

O

U

T

A

1

A

0

Table 4.10

Interface module data format for one reader (4 byte)

Note!

For some control panels, the position of the bytes in a word are swapped. For a description of 
the data bits, see chapter 5.4.

Summary of Contents for WCS DG310

Page 1: ...WCS DG310 WCS DeviceNet Interface Module FACTORY AUTOMATION MANUAL...

Page 2: ...Terms of Delivery for Products and Services of the Electrical Indus try published by the Central Association of the Electrical Industry Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in...

Page 3: ...on 7 4 Commissioning 9 4 1 Meaning of LEDs 9 4 2 Meaning of Switches 10 4 3 Operating Modes 11 4 4 Connecting the WCS Reader 12 4 5 Connection to the Control Panel 12 4 6 Data Exchange in DeviceNet 13...

Page 4: ...icable EU type examination certificate EU declaration of conformity Attestation of conformity Certificates Control drawings Instruction manual Other documents 1 2 Target Group Personnel Responsibility...

Page 5: ...in descending order as follows Informative Symbols Action This symbol indicates a paragraph with instructions You are prompted to perform an action or a sequence of actions Danger This symbol indicate...

Page 6: ...485 interface and from the WCS DG310 to the control panel via the DeviceNet protocol You can connect up to four WCS readers of type LS221 or LS121 If you connect several WCS readers they must have dif...

Page 7: ...2 to terminal 6 Tx 422 2 Connect terminal 5 Rx 422 to terminal 7 Tx 422 Note Grounding of the mounting rail The mounting rail must be grounded to the switch cabinet The connection wire must have a cro...

Page 8: ...ating voltage interface module operating voltage WCS reader 2 0 V Pwr Ground interface module ground WCS reader Table 3 2 Terminal X2 Caution Damage to the device Connecting an alternating current can...

Page 9: ...error and or warning number via the Error No Select ID LEDs BusState LED DeviceNet interface state Lights up green Connected to the DeviceNet master Flashes green No connection to the DeviceNet maste...

Page 10: ...or 0 1 1 0 6 Reserved 0 1 1 1 7 Communication WCS reader RS send buffer overflow 1 0 0 0 8 Communication WCS reader receive buffer overflow 1 0 0 1 9 Communication WCS reader RS timeout 1 0 1 0 10 Gen...

Page 11: ...EDs have no significance for the user The configuration mode is included in all software revisions Test mode Setting test mode Test mode is set by putting both switches S4 and S5 into position E No ot...

Page 12: ...0 You can connect up to 4 WCS readers to an interface module via an RS 485 cable The supplied default address of each WCS reader is 0 Refer to the configuration instructions for the WCS reader if you...

Page 13: ...DG310 you can only query the data from the master via polling access The sending of a function byte is likewise only possible in polling mode Polling In polling a function byte is sent from the master...

Page 14: ...s sent every 5 ms In this case the pause time is necessary to avoid overloading the DeviceNet bus Interface module data format for one WCS reader 4 7 EDS configuration file To assist with the configur...

Page 15: ...in line connection must end with a terminator The RS 485 terminators are integrated in the WCS readers and can be switched on and off with the interface module If only one WCS reader is connected one...

Page 16: ...WCS reader at the end of the data line For both WCS readers the RS 485 terminator is activated The interface module is located between these two heads and does not have an RS 485 terminator Each WCS...

Page 17: ...between the interface module and the first WCS reader through a short spur length 1 m Use a bus terminal to connect the spur Figure 5 3 Connection of two reading heads Version B The wiring version use...

Page 18: ...n Position and Speed operating mode 6 bytes are reserved for each WCS reader Pxx position data P00 LSB Sxx speed in multiples of 0 1 m s S00 LSB Example Byte 5 00011011 27 corresponds to 2 7 m s A1 A0...

Page 19: ...outside of the code rail not a position value Good P0 P18 0 WCS reader partly outside the code rail P0 1 P2 to P18 0 WCS reader completely outside of the code rail 1 0 0 Current position value binary...

Page 20: ...oss section and one pair for the RS 485 data line The table shows the possible cable lengths depending on the cable capacitance core core The number of connected WCS readers is of no significance SSI...

Page 21: ...S WCS DCF Capacitance core core 95 pF m 60 pF m Cross section 0 14 mm2 0 25 mm2 Number of wires 6 3 x 2 6 3 x 2 External diameter 5 8 mm 7 5 mm Temperature range 30 C 70 C 40 C 70 C Order designation...

Page 22: ...s GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com USA Headquarters Pepperl Fuchs Inc Twinsburg Ohio 44087 USA Tel 1 330 4253555 E mail sales us pepperl fuchs com Asia Pac...

Reviews: