Fieldbus Surge Protector
Installation
20
22
-0
6
27
3.2.2.2
Grounding rail ACC-LBF-EB.6
For attaching Surge Protectors to the spur connections of Fuchs fieldbus couplers
R2-SP*, R3-SP*, and F4D0-FB-IA*, the optional grounding rail ACC-LBF-EB.6 is used
to provide a common earth point and mechanical support for up to 6 SCP-LBF-1.36* modules.
For Surge Protectors that are placed on both sides of the fieldbus couplers, 2 grounding rails
ACC-LBF-EB.6 are required. If fieldbus couplers are used with less than 6 spurs on one side,
the grounding rail can easily be cut or snapped to length.
The grounding rail provides a screw clamp to be connected to an equal potential bonding
system using a minimum cross core section of 4 mm
2
.
3.2.2.3
Connect the Ground Cable at the Grounding Rail
1. Position the cable lug (3) over the grounding terminal of the grounding rail (4),
so that the cable points downwards.
2. Screw the cable lug (3) to the grounding terminal (4) using 2 toothed lock washers (2).
3. Tighten the screw with a torque of 1.5 Nm (1).
Internally, the shield connection of the trunk is directly connected to the grounding terminal
through a gas discharge tube.
3.2.2.4
Connect the Grounding Rail to the Grounding Terminal of the Housing
1. Position the cable lug (3) over the grounding terminal (4) so that the cable points
downwards.
2. Screw the cable lug to the grounding terminal (4) using 2 toothed lock washers (2).
3. Tighten the screw with a torque of 1.5 Nm (1).