EM-8066-B Rev.1 P. 1 / 2
SAFE INSTALLATION MANUAL (CENELEC APPROVAL)
LIGHTNING SURGE PROTECTOR FOR
F
OUNDATION
Fieldbus
(ultra-slim)
MODEL
MD7FB
BEFORE USE ....
■
SAFETY PRECAUTIONS
This manual describes important points of caution for safe
use of this product in potentially explosive atmosphere.
Please read this manual carefully before installing and op-
erating the product.
■
SPECIAL CONDITIONS FOR SAFE USE
Electrostatic charges on the enclosure shall be avoided.
■
MODEL NUMBER IDENTIFICATION
Model No. MD7FB – 1 2 3
1) SHIELD TERMINAL (to earth)
FF : Floating
FG : Grounding
2) SAFETY APPROVAL
0 : None
2 : CENELEC intrinsically safe (ATEX)
3) OPTIONS
-X : Special specification
■
MANUFACTURED DATE CODE IDENTIFICATION
The manufactured year and month can be identified by the
serial number described on the specification marking.
Serial No. Y M xxxxxx
YEAR
4 : 2014
A : 2020
1 : 2041
5 : 2015
B : 2021
2 : 2042
:
:
:
:
:
:
9 : 2019
U : 2040
9 : 2049
MONTH
1991 - 2019 (year)
2020 - 2052 (year)
A : January
M : January
B : February
N : February
C : March
P : March
:
:
:
:
L : December
Y : December
WARNING
Explosions could result in death or serious injury:
•
Before you remove the unit or mount it, or before you con-
nect or disconnect the wiring, turn off the power supply
and the input signal for safety. Do not disconnect unless
the area is known to be non-explosive.
•
Whenever you need to measure voltage across the termi-
nals or apply a simulated input signal to the terminals,
make sure that there is no danger of explosion in the at-
mosphere.
•
Verify the certification of the product described on the
specification marking on the product.
•
Verify that the operating atmosphere of the product is
consistent with the appropriate hazardous locations cer-
tifications.
•
Verify that the environmental temperature is within the
temperature class required for the area.
Failure to follow these installation guidelines could result
in death or serious injury:
•
Make sure only qualified personnel perform the instal-
lation.
SAFETY FEATURES & CAUTIONS
■
INTRINSICALLY SAFE APPROVAL
•
CENELEC / ATEX
EU-Type Examination Certificate: KEMA 08ATEX0166 X
0344
II 1G Ex ia IIC T4, T5
Zone 0
•
Applicable Standards
EN 60079-0
EN 60079-11
•
IS Data
LINEAR BARRIER
FISCO SUPPLY
Ui
32V
17.5V
Ii
any
400mA
Pi
See below
5.4W
Ci
5 nF
5 nF
Li
0 µH
0 µH
Pi : For T4 and Ta = -25 to 40°C : 1.3W
For T4 and Ta = -25 to 60°C : 1.2W
For T4 and Ta = -25 to 80°C : 1.0W
For T5 and Ta = -25 to 40°C : 1.0W
•
Install the product according to the installation diagram.
•
Install the product according to local installation codes.
•
DO NOT RUB the surface of the plastic enclosure with a
dry cloth. Electrostatic charge generated by the friction
may cause an explosion.
•
Max. continuous operating voltage (Uc)
Line to line: ±32V
Line to earth: ±160V
Shield to earth:
±160V (MD7FB-FF)
Shortcircuited for the MD7FB-FG