
20
21
-1
1
38
Power Supply PS1000-A6-24.20
Application Notes
26.2
Output Circuit Breakers
Standard miniature circuit breakers (MCB's or UL 1077 circuit breakers) are commonly used
for AC-supply systems and may also be used on 24V branches.
MCB's are designed to protect wires and circuits. If the ampere value and the characteristics
of the MCB are adapted to the wire size that is used, the wiring is considered as thermally safe
regardless of whether the MCB opens or not.
To avoid voltage dips and under-voltage situations in adjacent 24V branches which
are supplied by the same source, a fast (magnetic) tripping of the MCB is desired.
A quick shutdown within 10ms is necessary corresponding roughly to the ride- through time
of PLC's. This requires power supplies with high current reserves and large output capacitors.
Furthermore, the impedance of the faulty branch must be sufficiently small in order
for the current to actually flow. The best current reserve in the power supply does not help
if Ohm's law does not permit current flow. The following table has typical test results showing
which B- and C-Characteristic MCBs magnetically trip depending on the wire cross section
and wire length.
Figure 26.4 Test circuit
Maximal wire length
1
for a fast (magnetic) tripping:
0.75mm²
1.0mm²
1.5mm²
2.5mm²
C-2A
31m
37m
63m
98m
C-3A
28m
34m
51m
78m
C-4A
18m
25m
38m
58m
C-6A
9m
11m
18m
26m
C-8A
6m
7m
12m
14m
C-10A
4m
6m
11m
13m
C-13A
2m
2m
4m
7m
B-6A
23m
28m
46m
66m
B-10A
11m
14m
19m
32m
B-13A
7m
11m
16m
29m
B-16A
5m
6m
8m
15m
B-20A
1m
1m
2m
4m
B-25A
–
–
–
1m
1
Don’t forget to consider twice the distance to the load (or cable length) when calculating the total wire length
(+ and – wire).