Diagnostic Information and Troubleshooting
2
016-
06
41
7.2
Gateway Diagnostics
PROFINET DAP Module Channel Diagnostics
For the gateway and the motherboard, diagnostic information is available and mapped to the
DAP module channel diagnostics. The information is also available in the gateway device type
manager and web server.
Diagnostic
Message
Severity
ChannelDia
g ErrorType Possible Root Cause
Remedy/Next
Steps
Firmware
updated
need reboot
Maintenance
required
0x0103
The firmware version
has been updated.
Reboot.
ADM error or
module missing
Maintenance
demanded
0x0104
The advanced
diagnostic module
reports an error to the
gateway.
For further
analysis, access
the diagnostic
module via the
diagnostic
manager.
ADM system
maintenance
required
Maintenance
required
0x0105
The diagnostic module
reports a "Maintenance
required" alarm for the
Power Hub hardware.
ADM system out
of service
Maintenance
demanded
0x0106
The diagnostic module
reports an "Out of
specification" alarm for
the Power Hub
hardware.