Pepperl+Fuchs PMI360DV-F130-IU2E0-V15 Manual Download Page 24

PMI360DV-F130-IU2E0-V15

Troubleshooting

 2

0

1

9

-0

2

23

9.2

Faults During Operation

If the inductive angular positioning system does not function correctly, refer to the table below 
for possible causes and instructions for rectifying the problem.

Error

Possible cause

Action

"Power/Error" LED does not 
light up

The power supply is switched 
off.

Check whether there is a 
reason for it being switched off 
(installation or maintenance 
work etc.). Switch the power 
supply on if appropriate.

The cordset is not connected 
to the connector on the 
sensor.

Connect the cordset to the 
sensor and tighten the union 
nut by hand.

Wiring fault in the splitter or 
control cabinet.

Check the wiring carefully and 
repair any wiring faults.

Supply cable to the sensor is 
damaged.

Replace the damaged cable.

"Power/Error" LED lights up 
red permanently or 
intermittently.

No actuator in the detection 
area of the sensor or 
unreliable detection of the 
actuator.

Check that the actuator used 
is mounted correctly or install 
an actuator with appropriate 
dimensions at the correct 
distance from the sensor. (see 
chapter 5.2).

Analog current output yields a 
value of approx. 3.6 mA

No actuator in the detection 
area of the sensor or 
unreliable detection of the 
actuator.

Check that the actuator used 
is mounted correctly or install 
an actuator with appropriate 
dimensions at the correct 
distance from the sensor. (see 
chapter 5.2).

Actuator outside of 
parameterized measurement 
range.

Check that the position of the 
parameterized measurement 
range is correct.

Analog output does not reach 
the maximum value

Sensor operating voltage too 
low or load impedance out of 
specification.

Check the operating voltage of 
the sensor. Ensure that the 
load impedance is within the 
specified limits.see chapter 
7.2

No output signal at the 
switching output even though 
the associated LED lights up

Output cable not connected

Connect the output cable

Output cable is short circuiting Rectify the short circuit

Output signal outside the 
value range specified at the 
analog output

Load connected only after the 
sensor is switched on

Disconnect the sensor from 
the supply voltage. Switch on 
the sensor again 

with

 the load 

connected.

Switching output signal 
"chatters"

Use of a different actuator with 
incorrect dimensions or an 
incorrect distance to the 
sensor

Install an actuator according 
to specifications ()

Output signal unstable or 
unreliable

Actuator rotating too quickly

Make sure that the speed of 
the actuator is 

 100 

rotations/minute

Summary of Contents for PMI360DV-F130-IU2E0-V15

Page 1: ...PMI360DV F130 IU2E0 V15 Inductive Angle Positioning System FACTORY AUTOMATION MANUAL...

Page 2: ...of Delivery for Products and Services of the Electrical Indus try published by the Central Association of the Electrical Industry Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in its mos...

Page 3: ...Connection Cables 9 4 3 2 Actuator 10 5 Installation 11 5 1 Note on Safety 11 5 2 Mounting 11 5 3 Electrical Connection 12 6 Commissioning 14 6 1 Programming the Switching Outputs 14 6 2 Programming...

Page 4: ...4 PMI360DV F130 IU2E0 V15 9 Troubleshooting 22 9 1 Faults when Programming the Outputs 22 9 2 Faults During Operation 22 10 Disposal 24...

Page 5: ...worldwide scale Symbols used The following symbols are used in this manual Handling instructions You will find handling instructions beside this symbol Contact If you have any questions about the dev...

Page 6: ...developed and manufactured under observance of the applicable European standards and guidelines The product manufacturer Pepperl Fuchs GmbH D 68307 Mannheim has a certified quality assurance system t...

Page 7: ...ioning of all devices may only be performed by trained and qualified personnel User modification and or repair are dangerous and will void the warranty and exclude the manufacturer from any liability...

Page 8: ...log output for the analog indication of angular positions For high resistance loads 3 3 k the angular position is output as a voltage value 0 10 VDC and for low resistance loads 400 as a current value...

Page 9: ...utput and the outer S1 and S2 buttons are used to configure the start and end of the detection zone of the two switching outputs on the sensor The S1 S2 and I U LEDs correspond to the S1 S2 and I U pr...

Page 10: ...ordsets from our extensive range of accessories 4 3 2 Actuator The BT F130 A actuator is designed for mounting directly on the drive shaft or a servodrive Illustration Material Length Model number M12...

Page 11: ...r must not make physical contact or scratch the sensors surface when moving Using a different actuating element You may use a different actuator instead of the BT F130 A actuator provided When using a...

Page 12: ...inner surface E Sensor F Insert the shaft until actuator C and the sensitive surface on sensor D overlap as far as possible Dimension Value t 2 mm w 7 5 mm d1 Depends on the drive shaft material S235...

Page 13: ...Check that the wires are connected correctly before connecting the cordset to the sensor On Pepperl Fuchs cordsets the wire colors are assigned to the connecting pins in the connector according to DI...

Page 14: ...ed off which prevents the electrical output signal from wavering The switching hysteresis is located at the top or bottom end of the switching window depending on the direction of rotation of the actu...

Page 15: ...Move the actuator to the position that you wish to define as the switching window end point The actuator s direction of rotation is decisive here At the end of programming the area covered by the act...

Page 16: ...rocess is terminated The sensor continues operating with unchanged values Note If any other button is actuated the programming process is terminated The sensor continues operating with unchanged value...

Page 17: ...wise counterclockwise If the actuator rotates less than 30 the previously set direction of rotation is retained 6 Briefly press the I U button The setting is then stored in the non volatile memory of...

Page 18: ...t and end point are parameterized a measurement range of 360 is programmed The measurement range start point is then located in the position defined in the first step The previous preset direction of...

Page 19: ...Position of the second switching point of switching output S1 example 40 3 Position of the first switching point of switching output S1 example 60 4 Position of the first switching point of switching...

Page 20: ...s of actuator an active switching output changes to an idle state up position and a switching output already in an idle state remains in this state The Power Error LED lights up red when the actuator...

Page 21: ...when actuator is lost If the actuator leaves the sensing range of the angular positioning system e g actuator is removed the output logic depends on whether the analog output assumes the function of...

Page 22: ...e associated yellow LED starts to flash slowly after 2 seconds 2 Continue to hold the sensor button The LED begins to flash more quickly after an additional 10 seconds 3 Then release the button within...

Page 23: ...present or different actuator mounted too far away from the surface of the sensor Mount actuator according to specifications Power Error LED lights up red during programming Actuator lost during the p...

Page 24: ...No actuator in the detection area of the sensor or unreliable detection of the actuator Check that the actuator used is mounted correctly or install an actuator with appropriate dimensions at the corr...

Page 25: ...osal Electronic waste is hazardous waste When disposing of the equipment observe the current statutory requirements in the respective country of use as well as local regulations The device does not co...

Page 26: ...hs GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com USA Headquarters Pepperl Fuchs Inc Twinsburg Ohio 44087 USA Tel 1 330 4253555 E mail sales us pepperl fuchs com Asia Pa...

Reviews: