Commissioning
22
51
45 201
0-
03
EN - 19
EN
4
Commissioning
4.1
DIP switch settings
Switch
Description
DIP 1
NVF sensor
(NVF-104/34-PF)
ON
connected
OFF
not connected
DIP 2
KVF sensor
(KVF-104-PF)
or
SLU sensor
(SLU-103-**)
ON
connected
OFF
not connected
DIP 3
Acoustic alarm
ON
Acoustic alarm switched on.
OFF
Acoustic alarm switched off.
DIP 4
Relay setting
ON
Relays 1 and 2 switch in all alarm states. If an alarm event is no
longer pending, relay 1 switches back automatically AND relay 2
remains unchanged until the alarm has been acknowledged by
actuating "ALARM RESET". This shows therefore that an alarm was
present.
DIP 5
ON
DIP 4
Relay setting
ON
Relays 1 and 2 switch in alarm states. After 3 minutes, relay 2
switches back (even if an alarm state is pending). If the alarm state
disappears, relay 1 and/or relay 2 switches again. (If "ALARM
RESET" is actuated, the relays switch again)
DIP 5
OFF
DIP 4
Relay setting
OFF
Relay 1 switches with alarm state at NVF sensor; relay 2 switches
with alarm state at KVF sensor
or
SLU sensor. If the alarm state
disappears, relays 1 and/or 2 switch again (if "ALARM RESET" is
actuated, the relays switch again).
DIP 5
ON
DIP 4
Relay setting
OFF
Relays 1 and 2 switch in alarm states irrespective of which sensor.
If the alarm state disappears, relays 1 and/or 2 switch again
(if "ALARM RESET" is actuated, the relays switch again).
DIP 5
OFF
DIP 6
Repeat alarm
setting in
24 hours
ON
Repeat alarm setting switched on. This also applies to the function
of relays 1 and 2.
OFF
Repeat alarm setting switched off
DIP 7
Reset key
(ALARM RESET
activation)
ON
ALARM RESET is active. The acoustic alarm and the alarm relay
are reset.
OFF
ALARM RESET is deactivated. The acoustic alarm and the alarm
relay are not reset.
DIP 8
Not in use.