Fieldbus Power Hub,Motherboard for Gateway and Power Supply Modules
Installation and Commissioning
3
Installation and Commissioning
3.1
Mounting and Dismounting
Mounting of Fieldbus Motherboards on DIN Mounting Rail
In order to mount a motherboard on a DIN mounting rail, proceed as follows:
1. Place the motherboard on the DIN mounting rail.
2. Tighten the two fastening screws to attach the motherboard on the DIN mounting rail.
The motherboard has been mounted.
Mounting Plug-In Modules on the Motherboard
To install a new plug-in module on the motherboard, proceed as follows:
1. Carefully center the polarization holes and mate the 2 connectors, then gently press down
the module.
2. Push down the red Quick Lok bars on each side of the module to fix it to the panel. No tools
required.
Danger!
Danger to life from wrong mounting and installation
Incorrect mounting and installation of the device can compromise its function and its electrical
safety.
■
Observe the safety instruction in the instruction manual.
■
Observe the information in the manual.
Danger!
Explosion hazard from damaged electronic components
Premature wear of electronic components in a device that was previously used in a general
electrical installation can cause sparks that can ignite the surrounding potentially explosive
atmosphere.
Never install devices that have already been operated in general electrical installations in
electrical installations used in combination with hazardous areas!
Caution!
Property damage from wrong mounting
The Power Hub motherboard includes is a dedicated connection slot for the HD2-DM*
diagnostic modules labeled
“
Diagnostic Module only
“
. Using this slot for mounting the wrong
type of module can cause property damage on the module or the motherboard.
Do not try to plug other modules into this connection slot.