![Pepperl+Fuchs HCD2-FBPS Series Manual Download Page 10](http://html1.mh-extra.com/html/pepperl-fuchs/hcd2-fbps-series/hcd2-fbps-series_manual_1527738010.webp)
2
016-
06
10
Fieldbus Power Hub,Motherboard for Gateway and Power Supply Modules
Product Specifications
2.3
Component Identity and Dimensions
2.4
Technical Data
System Specification
MBHC-FB-4.GT*
1
Motherboard MBHC-FB-4.GT
2
Gateway module
3
Diagnostic module
4
Power supply modules (x 4)
5
Trunk connection
6
Shielding/grounding kit for trunk shields, optional accessory
7
Connections for alarm volt-free contact and diagnostic bus (x 2)
8
Connections for bulk power supply (x 2)
9
Rotary switches for gateway addressing x1, x10, x100
10
Shield connection
11
Mounting slot for DIN mounting rail
39 mm (1.5")
169 mm (6.6")
135 mm (5.3")
150 mm (5.9")
180 mm (7.1")
1
11
10
47
47
48
48
2
3
4
5
6
49
Ambient conditions
Ambient temperature
-40 ... 70
°
C (-40 ... 158
°
F)
Storage temperature
-40 ... 85
°
C (-40 ... 185
°
F)
Relative humidity
< 95 % non-condensing
Shock resistance
10 g , 11 ms
Vibration resistance
1 g , 10 ... 150 Hz
Pollution degree
max. 2, according to IEC 60664
Corrosion resistance
acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection type
plug-in terminals , spring terminal and screw terminal
Degree of protection
IP20