background image

© 2011 Pentair Technical Products

89083081

- 2 -

INSTALLATION INSTRUCTIONS

The Thermoelectric Temperature Controller can be mounted in any convenient dry location 

near the Thermoelectric Cooler (TEC). The location should take into consideration the 

desired position of the thermistor sensing bead and the length of the supplied thermistor 

harness, roughly 28 inches (700 mm) long. It is recommended, but not required, that the 

thermistor sensing bead be located at the inlet of the enclosure-side fan.
Mount the controller using the four supplied 10-24 self-tapping screws. Drill .172 inch 

(4.4mm) diameter pilot holes in the mounting plate using the .25 inches (6.4 mm) diameter 

holes near the corners in the back plate as a template. The cover must be removed to gain 

access to the mounting holes.

Power Supply

Class 2 power supply is required.

Wiring

With the exception of the thermistor, all wiring between the TEC and the controller, and 

between the controller and input power supply, is to be supplied by the user. Use copper 

supply wires.

Recommended wire gauges for wiring:

Power and earth ground inputs .................................14 AWG
TEC Module and earth ground outputs ...................14 AWG
Fan outputs ........................................................................20 AWG
Alarm outputs ...................................................................20 AWG

Description

Source

Destination

AWG

Input Power to Controller

External Power Source

TEC Controller

14

Input Earth Ground to Controller

External Earth Ground

TEC Controller

14

TEC Module Power

TEC Controller

TEC Terminal Block

14

TEC Module Earth Ground

TEC Controller

TEC Terminal Block

14

TEC Fan Power

TEC Controller

TEC Terminal Block

20

Alarm Outputs

TEC Controller

External Alarm Input

20

Connect the TEC as shown in the wiring diagrams, see Wiring Diagram on page 3. Ensure 

that higher potential conductor is connected to the (+) terminal and lower potential is 

connected to the (–) terminal. If heating is called for (as determined by the thermistor 

reading relative to the cooling and heating setpoints), the controller will automatically 

reverse the DC voltage to the TEC modules (peltier chips).

TABLE OF CONTENTS

INSTALLATION INSTRUCTIONS .............................................................................................2

Power Supply ..........................................................................................................................................2

Wiring .........................................................................................................................................................2

Wiring Diagram ......................................................................................................................................3

Setup ..........................................................................................................................................................4

Design Data .............................................................................................................................................5

Operation .................................................................................................................................................5

WARRANTY ...............................................................................................................................................6

RETURN AND REPAIR POLICY ............................................................................................................7

LIMITATION OF LIABILITY ....................................................................................................................7

RSPSupply  -  1-888-532-2706 -  www.RSPSupply.com

http://www.RSPSupply.com/p-6058-Hoffman-TEC24VCNTLR-Thermoelectric-Temperature-Controller-24V.aspx

Summary of Contents for TEC24VCNTLR

Page 1: ...tions Pentair Technical Products 2100 Hoffman Way Anoka MN 55303 1 763 323 8200 1 763 576 3200 www McLeanCoolingTech com INSTRUCTION MANUAL Thermoelectric Temperature Controller TEC24VCNTLR TEC48VCNTL...

Page 2: ...ended wire gauges for wiring Power and earth ground inputs 14 AWG TEC Module and earth ground outputs 14 AWG Fan outputs 20 AWG Alarm outputs 20 AWG Description Source Destination AWG Input Power to C...

Page 3: ...SUPPLIED WIRING CUSTOMER SUPPLIED WIRING THERMISTOR HARNESS INCLUDED WITH CONTROLLER THERMOELECTRIC TEMPERATURE CONTROLLER ALARM OUT EARTH GROUND INPUT POWER WIRE TO TERMINAL 4 FOR THESE UNITS ONLY W...

Page 4: ...sition Temperature setpoint dip switch position tables Cool 1 2 3 Cooling Set Point F C ON ON ON 95 0 35 0 factory set ON ON OFF 90 5 32 5 ON OFF ON 86 0 30 0 ON OFF OFF 81 5 27 5 OFF ON ON 77 0 25 0...

Page 5: ...ode with no power applied to the TEC modules When going from cooling to heating or heating to cooling the control logic provides for a minimum ten minute delay when applying power to the peltier chips...

Page 6: ...in any way or 1 Buyer specified product is inappropriate for system or environment in which it is operating 2 Pentair Technical Products product modified in any way without prior written authorization...

Page 7: ...etermined by Pentair Technical Products not be covered under warranty Buyer will be responsible for all shipping charges and will be billed accordingly H Non warranty repairs are subject to a 75 minim...

Page 8: ...Protecting Electronics Exceeding Expectations Pentair Technical Products 2100 Hoffman Way Anoka MN 55303 1 763 323 8200 1 763 576 3200 www McLeanCoolingTech com RSPSupply 1 888 532 2706 www RSPSupply...

Reviews: