© 2013 Pentair Equipment Protection
88004712
- 4 -
INSTALLATION INSTRUCTIONS
1. Inspect the air conditioner and verify correct functionality before mounting the air conditioner. See
HANDLING AND TESTING THE AIR CONDITIONER on page 3.
2. Determine if the unit is to be surface or recess mounted. Using the appropriate cutout dimensions,
see MOUNTING CUTOUT DIMENSIONS on page 5 of this manual. Prepare the enclosure
opening for either surface or recess mounting.
3. Using the gasket kit provided, install gaskets to air conditioner.
4. Mount air conditioner on enclosure using mounting bolts and screws provided. Allow unit to
remain upright for a minimum of five (5) minutes before starting. Caution! Air conditioner must be
in upright position during operation.
5. When routing the drain tube, caution should be taken to keep it from kinking or being elevated
above the exit point of the air conditioner. The drain tube must be on a continuous downward
slope. A slight elevation of the tube could result in secondary trap. FAILURE TO FOLLOW THESE
INSTRUCTIONS COULD RESULT IN OVERFLOWING OF THE CONDENSATE DRAIN PAN.
6. Refer to top of nameplate for electrical requirements. Connect the power cord to a properly
grounded power supply. Use of an extension cord is not recommended. Electrical circuit should be
fused with slow blow or HACR circuit breaker.
DESIGN DATA
Model
Voltage
Hz
Full Load
Amps
Phase
BTU/Hr @ Max
Amb Temp
Max Amb Temp
°F/°C
Shipping
Weight lb./kg
T531926GXXX
230
50/60
17.3/20.3
1
16,800/19,000
131/55
197/89
XXX will be replaced with a three-digit number designating all desired options. Consult the factory for specific model numbers.
DIMENSIONAL DRAWING