Reset
RS-485-1
Termination
Pull-down
Pull-up
Termination
3 2 1
ON
RS-485-2
Termination
rs-485 configuration switches
reset switch
The configuration switches are found on the right side of the
NGC-UIT2-ORD. Refer to the table below for settings.
The Reset switch can be found on the side of the NGC-UIT2-ORD. A
pointed object is required to press the reset switch and restart the
NGC-UIT software.
position
switch
on
off
comments
Pull-down
(As-shipped default) RS-485 network
“–” signal is forced to a determinate
state when idle.
RS-485 network “–” signal is not
forced to a determinate state when
idle.
One device (typically this NGC-UIT2-ORD) on the
RS-485 network should force the network “-“ signal
to a determinate state.
Pull-up
(As-shipped default) RS-485 network
“+” signal is forced to a determinate
state when idle.
RS-485 network “+” signal is not
forced to a determinate state when
idle.
One device (typically this NGC-UIT2-ORD) on the
RS-485 network should force the network “+“ signal
to a determinate state.
Termination
(As-shipped default) RS-485 network
is terminated with 120-ohm resistor.
RS-485 network is not terminated.
Terminate the device (NGC-UIT2-ORD or other) that
is at each end of the RS-485 network, for a total of
two terminated devices. No other devices on the
network should be terminated.