Pentair Raychem NGC-UIT2-0RD Installation Instructions And Specifications Download Page 1

NGC-UIT2-ORD 

installed in a panel

Description

The NGC-UIT2-ORD is a panel mounted display used in conjunction 

with other Raychem control and monitoring devices. The NGC-UIT2-

ORD is rated IP 65 (Type 4), and can be mounted indoors or outdoors. 

The NGC-UIT2-ORD kit includes all hardware required for mounting 

in a suitable electrical panel. Additional materials are required for 

electrical connections and are detailed below. These instructions 

describe how to mount the NGC-UIT2-ORD in an electrical panel and 

are intended only for personnel experienced in panel construction.

tools requireD

•  Masking tape 

•  #16 (3/16) drill bit

•  Metal file

•  In-line torque wrench with 8 mm (5/16 in) socket

•  Jig saw (recommend using carbon steel blade with 24TPI)

ADDitionAl MAteriAls (to be orDereD sepArAtely)

qty Description

Manufacturer

Manufacturer  

part number

2

9 pin D-SUB to 10 pin terminal 

block PCB

Phoenix Contacts

2315162

2 Serial communication cable

L-COM

CSMN9MF-xx

 

xx = Length in ft

3 Alarm relays – 12 Vdc, 12 A, 

SPDT

Tyco Electronics

RTB14012F

3

Alarm relay sockets

Tyco Electronics

RT78724

1 Push to test alarm light 120 or 230 Vac

note

: Equivalent parts may be used.

FIRE HazaRd

: The NGC-UIT2-ORD must not be used in hazardous 

locations. Electrical components within the unit could ignite 

flammable gases. Do not install the unit where it may be exposed 

to flammable gases.

The NGC-UIT2-ORD is an electronic unit. During installation, take the 

following precautions to avoid damage to its electronic components.

•  Handle with care to avoid mechanical damage.
•  Keep electronics dry.
•  Avoid exposure to static electricity.

•  Avoid contamination with metal filings, liquids, or other foreign 

matter.

•  Take care to protect the user interface board on the enclosure door.
•  Use agency-approved conduit bushings, adapters, and cable 

glands to keep the enclosure protected from dust and fluids.

WARNING:

IMPORTANT:

General

Area of Use

Nonhazardous, indoors or outdoors  

(IP65, Type 4)

Supply Voltage

9 – 30 Vdc, 3.6 – 1.2 A

Operating 

Temperature

–30°C to 50°C (–22°F to 122°F)

Min. Storage 

Temperature

–30°C to 80°C (–22°F to 176°F)

Dimensions

279 mm W X 229 mm H X 70 mm D

 

(11 in. W X 9 in. H X 2.75 in. D)

Alarm outputs

Transistor open 

collector outputs

Three open collector outputs, with a range of 5 – 30 

Vdc with a max. sink current of 500 mA

Use to drive

external relays

Relays may be assigned for alarm outputs.

lcD Display 

Display

LCD is a 8.4 in. XGA, color TFT transflective device 

with integral LED backlight

Touch Screen

5-wire resistive touch screen interface for user entry

network connection

Local/

 

Remote Port

RS-232/RS-485 ports may be used to communicate 

with host computers (Raychem Supervisor Software) 

or DCS

Local RS-232

A non-isolated, 9 pin D sub male

Remote RS-485 #2

2-wire isolated, 9 pin D sub male

Data Rate

9600 to 57600 baud.

Maximum cable 

length

For RS-485 not to exceed 1200 m (4000 ft). Cable to 

be shielded twisted pair.

Field Port 

RS-485, 2-wire isolated. Used to communicate with 

external devices, such as NGC-30-CRM and RMM2. 

Maximum cable length not to exceed 1200 m (4000 

ft). Cable to be shielded twisted pair.

Field RS-485 #1

2-wire isolated, 9 pin D sub male

Data Rate

To 9600 baud

LAN

10/100 Base-T Ethernet port with Link and Activity 

Status LEDs

USB Ports

USB 2.0 Host port Type A receptacle (X2)

ApprovAls / certificAtions

3128486

CONFORMS TO UL STD 60950-1

CERTIFIED TO CSA STD C22.2 

NO. 60950-1

Nonhazardous Locations

1 / 8

GB-RaychemNGCUIT20RD-IM-H58531     INSTALL-168      05/15

inDustriAl HeAt trAcinG solutions

NGC-UIT2-ORD

User Interface termInal for raychem nGc systems InstallatIon InstrUctIons

Summary of Contents for Raychem NGC-UIT2-0RD

Page 1: ... to protect the user interface board on the enclosure door Use agency approved conduit bushings adapters and cable glands to keep the enclosure protected from dust and fluids WARNING IMPORTANT General Area of Use Nonhazardous indoors or outdoors IP65 Type 4 Supply Voltage 9 30 Vdc 3 6 1 2 A Operating Temperature 30 C to 50 C 22 F to 122 F Min Storage Temperature 30 C to 80 C 22 F to 176 F Dimensio...

Page 2: ...mbly in Panel 1 Provide suitable panel enclosure To protect its electronic components the NGC UIT2 ORD must be mounted in a non hazardous location panel with a minimum IP32 Type 1 enclosure An IP52 Type 12 or better enclosure is recommended The NGC UIT2 ORD assembly comes with a sealing gasket and hardware to mount the enclosure Note The Raychem NGC UIT2 ORD is designed for opera tion in ambient t...

Page 3: ...st easily accomplished if the panel door is on a horizontal surface 5 Mount the user interface assembly onto the panel door Place the NGC UIT2 ORD assembly in position the twelve studs go through the twelve holes on the NGC UIT2 ORD assembly mounting plate see figure below Place the supplied 6 32 in Kep nuts on each of the twelve mounting studs Fasten only hand tight Look at the front of the panel...

Page 4: ... 426 in 88 39 mm 3 480 in Ø 4 8 3 m m 0 1 9 0 i n X 1 2 71 48 mm 2 814 in 71 48 mm 2 814 in 71 48 mm 2 814 in Panel Cut Out Area Top of Display Drawing NOT TO SCALE Drawing NOT TO SCALE 11 1 mm 0 437 in 88 39 mm 3 480 in 88 39 mm 3 480 in 243 54 mm 9 588 in Panel Cut Out Panel Cut Out NGC UIT2 ORD Cut Out Dimensions ...

Page 5: ...NS Bottom view Back view Front view RS 485 2 Debug Port not used Ethernet USB device port not used Open Collector Outputs RS 485 1 Side view Side view RS 232 RS 485 1 Termination RS 485 2 Termination USB Power RS 485 not used CAN not used RS 485 not used NGC UIT2 ORD Connection Diagram ...

Page 6: ...g located on the left side of the NGC UIT2 ORD The lead should go to the terminal marked 9 30 Vdc and the lead should go to the terminal marked GND Note The NGC UIT2 ORD is rated for 9 30 Vdc Since the NGC 30 CRM modules are rated for 12 Vdc we have used this voltage to also power the NGC UIT2 ORD As a result the recommend alarm relays and lights detailed in the Additional Materials are rated for ...

Page 7: ... the same Install the two 9 pin D SUB to 10 pin terminal block on a DIN rail inside the panel enclosure Note These should be placed were the Serial cable from the bottom of the NGC UIT2 ORD mounted on the panel door can be easily accessible Connect one end of the Serial communication cables to the ports labeled RS 485 1 and RS 485 2 on the touch screen and the other ends to the 9 pin D SUB to 10 p...

Page 8: ...e NGC UIT2 ORD Refer to the table below for settings The Reset switch can be found on the side of the NGC UIT2 ORD A pointed object is required to press the reset switch and restart the NGC UIT software Position Switch On Off Comments Pull down As shipped default RS 485 network signal is forced to a determinate state when idle RS 485 network signal is not forced to a determinate state when idle On...