Pentair Raychem NGC-UIT2-0RD Installation Instructions And Specifications Download Page 7

7 / 8

GB-RaychemNGCUIT20RD-IM-H58531     INSTALL-168      05/15

INDUSTRIAL HEAT TRACING SOLUTIONS

To CRM/S, 

RMM or

NGC-20

To host

computer

Data +

Shield

Data –

5 4 3 2 1

T 9 8 7 6

Field Port

RS-485-1

Data +

Shield

Data –

Remote Port

RS-485-2

Remote Port

Field Port

Back Side of UIT

RS-485-2 RS-485-1

5 4 3 2 1

T 9 8 7 6

communication

The NGC-UIT2-ORD has two isolated RS-485 ports located at 

the bottom.

field side port (rs-485-1)

The RS-485 port labeled “RS-485-1” is the field side port 

that is used to communicate with ModBus devices (ie. NGC-

30-CRM/S, RMM2 and NGC-20).

Host port (rs-485-2) – optional

The RS-485 port labeled “RS-485-2” is the Host side port 

that is used to communicate with to a host computer (using 

Raychem Supervisory Software) or to a DCS.

local Host port (rs-232) – optional

The RS-232 port can be used as local Host port that is used 

to communicate with to a host computer (using Raychem 

Supervisory Software). If the RS-232 port is utilized, the 

supplied female to female, 9-pin null modem adaptor cable 

must be used.

connection

The wiring connection to both RS-485-1 and RS-485-2 are the 

same.

Install the two 9 pin D-SUB to 10 pin terminal block on a DIN 

rail inside the panel enclosure. (Note: These should be placed 

were the Serial cable from the bottom of the NGC-UIT2-ORD 

mounted on the panel door can be easily accessible).
Connect one end of the Serial communication cables to the 

ports labeled RS-485-1 and RS-485-2 on the touch screen and 

the other ends to the 9 pin D-SUB to 10 pin terminal block. 

(

note

: The lengths of Serial communication cables are based 

upon were the touch screen is located and the 9 pin D-SUB to 

10 pin terminal block. You should locate these parts first, mea

-

sure, and then purchase your Serial communication cables).

Using a shielded, twisted pair cable ( Belden CDT cable 8761 

or equivalent, maximum length is 1219 meters (4000 feet), 

connect to terminals 3 (–) and 4 (+) on the 9 pin D-SUB to 10 pin 

terminal blocks taking note of the polarity.

The NGC-UIT2-ORD contains no user-serviceable parts. Contact 

your Pentair Industrial Heat Tracing Solutions representative for 

service and an authorization number if required.

The touch screen area of the NGC-UIT2-ORD may be cleaned 

with a damp or dry cloth. Typical window cleaning agents may be 

applied to aid in the removal of dirt, dust and grease. 

Do not use 

abrasive cleaners.

servicing

cleaning

Summary of Contents for Raychem NGC-UIT2-0RD

Page 1: ... to protect the user interface board on the enclosure door Use agency approved conduit bushings adapters and cable glands to keep the enclosure protected from dust and fluids WARNING IMPORTANT General Area of Use Nonhazardous indoors or outdoors IP65 Type 4 Supply Voltage 9 30 Vdc 3 6 1 2 A Operating Temperature 30 C to 50 C 22 F to 122 F Min Storage Temperature 30 C to 80 C 22 F to 176 F Dimensio...

Page 2: ...mbly in Panel 1 Provide suitable panel enclosure To protect its electronic components the NGC UIT2 ORD must be mounted in a non hazardous location panel with a minimum IP32 Type 1 enclosure An IP52 Type 12 or better enclosure is recommended The NGC UIT2 ORD assembly comes with a sealing gasket and hardware to mount the enclosure Note The Raychem NGC UIT2 ORD is designed for opera tion in ambient t...

Page 3: ...st easily accomplished if the panel door is on a horizontal surface 5 Mount the user interface assembly onto the panel door Place the NGC UIT2 ORD assembly in position the twelve studs go through the twelve holes on the NGC UIT2 ORD assembly mounting plate see figure below Place the supplied 6 32 in Kep nuts on each of the twelve mounting studs Fasten only hand tight Look at the front of the panel...

Page 4: ... 426 in 88 39 mm 3 480 in Ø 4 8 3 m m 0 1 9 0 i n X 1 2 71 48 mm 2 814 in 71 48 mm 2 814 in 71 48 mm 2 814 in Panel Cut Out Area Top of Display Drawing NOT TO SCALE Drawing NOT TO SCALE 11 1 mm 0 437 in 88 39 mm 3 480 in 88 39 mm 3 480 in 243 54 mm 9 588 in Panel Cut Out Panel Cut Out NGC UIT2 ORD Cut Out Dimensions ...

Page 5: ...NS Bottom view Back view Front view RS 485 2 Debug Port not used Ethernet USB device port not used Open Collector Outputs RS 485 1 Side view Side view RS 232 RS 485 1 Termination RS 485 2 Termination USB Power RS 485 not used CAN not used RS 485 not used NGC UIT2 ORD Connection Diagram ...

Page 6: ...g located on the left side of the NGC UIT2 ORD The lead should go to the terminal marked 9 30 Vdc and the lead should go to the terminal marked GND Note The NGC UIT2 ORD is rated for 9 30 Vdc Since the NGC 30 CRM modules are rated for 12 Vdc we have used this voltage to also power the NGC UIT2 ORD As a result the recommend alarm relays and lights detailed in the Additional Materials are rated for ...

Page 7: ... the same Install the two 9 pin D SUB to 10 pin terminal block on a DIN rail inside the panel enclosure Note These should be placed were the Serial cable from the bottom of the NGC UIT2 ORD mounted on the panel door can be easily accessible Connect one end of the Serial communication cables to the ports labeled RS 485 1 and RS 485 2 on the touch screen and the other ends to the 9 pin D SUB to 10 p...

Page 8: ...e NGC UIT2 ORD Refer to the table below for settings The Reset switch can be found on the side of the NGC UIT2 ORD A pointed object is required to press the reset switch and restart the NGC UIT software Position Switch On Off Comments Pull down As shipped default RS 485 network signal is forced to a determinate state when idle RS 485 network signal is not forced to a determinate state when idle On...

Reviews: