parameters
alarms
The first parameter displayed during set-up mode
is units (°F or °C). Other parameters, their default
values, and minimum and maximum values, are
shown in the following table.
The following table lists the error or alarm codes
and their respective faults:
Alarm Relay
Form C: 2 A at 277 Vac, 2 A at 48 Vdc
Normally energized; changes state upon an alarm.
note:
1. The minimum high temperature alarm set point must always be larger than the maintain set
point plus the deadband plus 5°F (3°C).
2. The maximum low temperature alarm set point must always be smaller than the maintain set
point minus the deadband.
display code
parameter
default
Min.
Max.
1
Units
°F or °C
°F
—
—
2
Maintain
set point
40°F
32°F (0°C)
425°F (218°C)
3
Deadband
5°F
2°F (2°C)
10°F (10°C)
4
High Alarm
1
Off
38°F (3°C)
482°F (250°C)
5
Low Alarm
2
Off
20°F (–6°C)
420°F (216°C)
alarm / error codes
Fault
rtd Err
Shorted or open RTD sensor
Hi Alr
High Temperature Alarm
Lo Alr
Low Temperature Alarm
IndustrIal Heat tracIng sOlutIOns
EN-RaychemJBS100ECPA-IM-H57463 05/16
NOrtH aMerICa
Tel: +1.800.545.6258
Fax: +1.800.527.5703
Tel: +1.650.216.1526
Fax: +1.650.474.7711
eurOPe, MIddle east, afrICa
Tel: +32.16.213.511
Fax: +32.16.213.603
asIa PaCIfIC
Tel: +86.21.2412.1688
Fax: +86.21.5426.2937
latIN aMerICa
Tel: +1.713.868.4800
Fax: +1.713.868.2333