IndustrIal Heat tracIng sOlutIOns
EN-RaychemJBS100ECPA-IM-H57463 05/16
Optional
Alarm
Contacts
Com
NC
NO
To user
annunciation panel
Line
Line/ Neutr
al
Earth
Power
Terminal
Block
Power In
Pentair Thermal
Management
recommends
the use of a
conduit drain to
prevent water
condensation
build-up
10
11
connecting alarm
• The controller has a form C contact for remote
annunciation of low and high alarms. If an external
alarm is required, then alarm wiring can exit the
enclosure via the 3/4 inch power conduit hole, as long
as the insulation rating of the alarm wire is equal to
the power wire. (Per NEC 303-3 (c)).
Alarm Relay
Form C: 2 A at 277 Vac, 2 A at 48 Vdc
Normally energized; changes state upon an alarm.
• Install conduit and fittings as
shown. To minimize loosening
due to pipe vibration, use
flexible conduit.
• Pull in power and ground
wires, strip off 1/2 in (13 mm)
of insulation and terminate.
11 / 14
Earth
Line/ Neutr
al
Line
Power
Terminal
Block
To
Heating
Cable
MI heating cable
Grounding strap
RTD
Input
R R W
Red
White
8
9
connecting Heating cable
• Insert the two heating
cable wires into the
terminal block marked
“To Heating Cable” and
the grounding strap
to “Earth” and tighten
terminals. Confirm
connection by pulling
on the wires.
connecting rtd
• Insert the three RTD wires into
the terminal block marked “RTD
Input”. Match the colors (Reds
to R, White to W), and tighten
terminals. Confirm connection by
pulling on the wires.