Installation and Inspection
Records
Raychem-IM-H58067-IceStopRoofGutterDeIcingCOM-EN 18/01
Maintenance log Record
Area location:
System
Reference drawing(s)
CIRCUIT INFORMATION
Breaker panel number:
Supply voltage
Phase
vISUAl
Heating system connection kits
Controller and sensor
Enclosures, junction boxes, contactors sealed
Signs of corrosion/damage
Presence of moisture
Delay timer set
Signs of corrosion
Damage to termination
ElECTRICAl TESTING
Perform insulation resistance test at 500, 1000, and 2500 Vdc
(bypass controller if applicable)
WARNING:
Disconnect all power before performing insulation resistance
and continuity tests.
Heating
Heating cable
cable
Breaker
catalog no. /tag no.
location
number
500 vdc
1000 vdc
2500 vdc
Cable #1
Cable #2
Cable #3
Cable #4
Cable #5
Cable #6
Cable #7
Cable #8
Cable #9
Cable #10
Cable #11
Cable #12
Ground-fault protection (type)
Ground-fault trip setting
mA
Test ground fault
Test controller
Comments and actions
Prepared by:
Company
Date
Approved by:
Company
Date