THERMAL BUILDING SOLUTIONS
EN-RaychemECWGF-IM-H58339 03/15
9 Volt
battery
(not supplied)
Menu
Down
Up
Next
1A
2
1B
Powering Controller via Battery
(This option allows programming the controller prior to powering
the heating cable and controller circuit.)
• Connect 9 Vdc battery (not provided) to the supplied
battery connector.
• Plug the battery connector onto the two pins on the
controller marked “Battery Connector.”
Activating and Navigating the Menu in Set-up Mode
• To activate set-up mode, press
Menu
button for
approximately 3 seconds.
• The display will change to the default mode for units.
• Use the
Up
and
Down
buttons to change values.
Use the
Next
button to change to next display code/
parameter.
• When completed, secure the enclosure cover.
Powering Controller via Line Power
• Turn on branch circuit breaker that supplies power to the
controller and heating cable.
WARNING: Shock Hazard. Secure the wire cover in
place with the four screws before energizing circuit.
6
• Install wire cover by attaching it to plastic stand-offs.
• Program the controller. (See the section
“Programming the Controller” that follows.)
• Install lid.
• Leave these instructions with the end user for
future reference.
Programming the Controller
To program the controller, supply voltage to the controller in either of the following ways.