2 / 6
THERMAL BUILDING SOLUTIONS
EN-RaychemECWGF-IM-H58339 03/15
Max. screw size: 5/32 in (4 mm)
Hole size:
0.25 in (6.4 mm) x 4
Right side entry:
3/4 NPT (1.09 in)
Bottom entry:
1 in NPT (1.29 in)
Left side entry:
1/2 in NPT (0.86 in)
1 in to 1/2 in reducing bushing
to RayClic-PC or FTC-P
Earth
Line/ Neutr
al
Line
Line/ Neutr
al
Line
Power
Terminal
Block
To
Heating
Cable
Power
In
Heating cables
using RayClic
power connection kit
Heating cables
using FTC-P
power connection kit
to RayClic-P
or FTC-P
or MI heating cable
Metal Junction Box
Incoming
Power
Line Gr
ound
Line / Neutr
al
Earth
Line/ Neutr
al
Line/ Neutr
al
Line
Line
Power
Terminal
Block
To
Heating
Cable
Power
In
1
2A
2B
• Attach box to wall using the
appropriate mounting fasteners.
Heating cable directly connected to
the ECW-GF controller
• Insert the two heating cable power
wires from the heating cable’s
junction box into the terminal block
marked “To Heating Cable” and
the ground (braid) marked “Earth”
and tighten terminals. Confirm
connection by pulling on the wires.
• For directly connected MI cable, you
must us a 1 to 1/2 inch reducing
bushing with grounding hub.
Connecting heating cable using a
separate junction box
Wall mounting the ECW-GF controller