Connections
7
Output Connections (See Figure 5, Page 7):
See Table 6, Page 15, for correct wires sizes, VFD to motor.
The output of
PID2000
Series drives is 220V
single phase
power.
The output power terminals (motor wire connections) are
located on the lower right side of the drive and are labeled
R (Red), Y (Yellow), and B (Black). Feed the motor cable
through the 20mm conduit hole on the bottom right side
and into the appropriate terminals. If the wire is large
enough to require a larger conduit hole, remove the 32mm
knockout and use the appropriate conduit connections.
Attach the motor ground wire to the grounding lug, located
to the upper right of the terminal block. Attach the motor
power wires to the terminals as shown in Figure 5. Table 3
lists the required wire color attachment scheme.
Table 3: Motor Wiring Connections
Pressure Tank Recommendations:
Minimum tank size is 8 litres. Use a pre-charged pressure
tank with the Drive. The tank size must equal at least 20%
of the pump’s rated flow in litres per minute (LPM), but
cannot be less than 8 litres capacity. For example, a pump
rated at 30 LPM would require a tank of 8 litres capacity
or larger. A pump rated at 150 LPM would require a
30 litre tank or larger. A larger tank may increase cycling
of the pump.
Table 4: Control Pressure Set Point and
Tank Pre-Charge Pressure Values
NOTE:
Set the pressure tank’s pre-charge to 70% of the
system operating pressure. When using an external set
point as well as an internal set point, pre-charge the tank
to 70% of the lower set point of the two. Some
applications may require a different percentage when
figuring the set point.
Transducer Connections (See Figure 5):
Use the transducer provided with the drive. Install the
transducer downstream of the tank. Install the transducer in
a tee in a straight section of pipe with at least 1 foot of
straight pipe on each side of the tee (that is, all fittings
must be at least one foot away from the transducer).
Feed the transducer cable through the open 12mm conduit
hole on the bottom of the drive enclosure.
Pressure Setpoint
Precharge Pressure
(kPa)
(kPa)
200
140
250
175
300
210
350
245
400 (Default)
280
450
315
500
350
550
385
600
420
650
455
Aust
EUR
USA
Code
Main/Run Winding
Blue
Blue/Grey
Black
B
Start/Aux Winding
White
Black
Red
R
Common
Red
Brown
Yellow
Y
Cable Shield
Red to AI+
Black to AI–
Transducer Cable
Connections
Submersible Motor:
3-W. 1-Ph.,
follow colors as shown in Table 3.
Cable Shield Lug
Output Ground Screw
Input Power Connections
Input Ground Screw
See Figures 6–9, Page 12, for information
about I/O Connections O1, I1,V+, and V–.
Green/Yellow
(Ground)
Green/Yellow
(Ground)
6184 0310 EX
Figure 5: Basic Wiring Connections for Startup.