Do not allow loose foreign objects which can conduct
electricity (such as screws and metal fragments) inside
the VFD box at any time. Do not allow flammable
substances (such as oil) inside the VFD box at any
time.
• Ground the VFD according to the requirements of the
Wiring Rules (AS/NZS 3000) and any other codes and
ordinances that apply.
•
All installation, service work, and inspections must be
done by a qualified electrician.
Carefully read and follow all safety instructions in this
manual or on device.
PENTEK INTELLIDRIVE Includes:
• PENTEK INTELLIDRIVE
TM
• Pressure Transducer
• 3 Metre Pressure Transducer Cable
• Quick Start Guide
• Owner’s Manual
The PENTEK INTELLIDRIVE is specifically designed to
operate 4” submersible pumps. Each drive is rated for
maximum output amp rating. Any use of the drive
outside of its intended use and design parameters will
void the warranty.
Transducer
The drive uses a 4-20mA, 0-690 kPa pressure transducer to
control the speed of the motor.
The transducer senses pressure in the pipe and converts it
to an electrical signal which it sends to the drive. The drive
processes the signal in the PID (Proportional, Integration,
Derivative) control. When operating in PID mode the drive
increases and decreases the speed of the pump motor as
needed to maintain constant pressure in the system.
Description / Typical Installation
4
6226 0710
Transd
u
cer; install in straight
pipe at least 32 cm a
w
ay from
pipe fittings on each side.
N
OTE: Enclos
u
res rated IP22
req
u
ire
W
ater Proof Ca
b
le Gland
G
N
D
20 cm
or more
20 cm
or more
Figure 1: Overall Layout – Typical installation