Controller Initial Power-Up
• The water supply valve should be off or be in by-pass
• At initial power-up, the camshaft may need to rotate to the HOME (in service) position.
• Camshaft may take 1 to 2 minutes to return to HOME position.
• Err 3 will be displayed until the camshaft returns to HOME position (Initial Power-Up
Display).
• If more than 2 minutes lapse, verify that the motor is turning the camshaft. If not, check
the “Troubleshooting” section.
Initial Power-Up Display
When the camshaft has reached the HOME (service) position the display will show “- -:- -”.
If the time of day alternating with filtered water volume is displayed, then the controller
has used its short term memory to load settings. Short term memory will hold settings for
approximately eight hours.
Initial Startup settings
The description above guides the system parameters.
• Time of day: current time
• ’Backwash Duration’ and ‘Cleaning Cycle Interval’ be set according below table.
PCFE40P12
TSS(NTU)
Cleaning Cycle Interval(t)
Backwash Duration(min)
<1
5
8
1.0-2.0
5
12
>2
5
20
PCFE54P12
TSS(NTU)
Cleaning Cycle Interval(t)
Backwash Duration(min)
<1
9
8
1.0-2.0
9
12
>2
9
20
Notes: if - TSS value, suggest setting 20 min for backwash duration.