background image

© 2016  Pentair Equipment Protection

87567377

- 7 -

MAINTENANCE PROCEDURES

• 

Disconnect all power supplies to the air conditioner before performing any service inside the unit.

• 

Operation of the air conditioner in areas containing airborne caustics or chemicals can rapidly 

deteriorate filters, condenser coils, blowers and motors, etc. Contact Pentair Equipment Protection for 

special recommendations.

• 

In accordance with section 608 of the Clean Air Act, no person maintaining, servicing, repairing or 

disposing of appliances may knowingly vent or otherwise release into the environment any class I or 

class II substance used as refrigerant.

CAUTION

MAINTENANCE INFORMATION

• 

Always disconnect the power before inspecting or working on the unit.

• 

Access the filter by lifting off the grille.

• 

The filter is reusable and can be cleaned by flushing with water.

• 

For additional filtering capacity, coat both sides of the filter with filter adhesive (catalog number AFLTAD)

COMPRESSOR

The compressor requires no maintenance. It is hermetically sealed, properly lubricated at the factory and 

should provide years of satisfactory operating service.
Should the refrigerant charge be lost, recharging ports (access fittings) on the suction and discharge sides 

of the compressor are provided for recharging and/or checking suction and discharge pressures.
In the event that service is required, use only certified refrigeration repair service personnel. Consult your 

local listing for commercial air conditioning maintenance establishments.

REFRIGERANT LOSS

Your air conditioner was thoroughly tested before leaving the factory to insure against refrigerant leaks. 

Shipping damage or microscopic leaks not found with sensitive electronic refrigerant leak-detection 

equipment during manufacturing may require repair and recharging of the system. This work should be 

performed by qualified professionals only, generally available in any reputable air conditioning repair or 

service company in your local area.
Refer to the data on your nameplate which specifies the type of refrigerant and the charge sizes in ounces.
Prior to recharging, the system must be evacuated and checked for leaks.

FANS AND MOTORS

Fan motors require no maintenance. All bearings, shafts, etc. are lubricated during manufacturing for the 

life of the motor. Access for fan replacement requires the removal of the air conditioner shroud.

CONDENSER AND EVAPORATOR

Condensers and evaporator coils are constructed with copper tubes with mechanically bonded aluminum 

fins. No maintenance is ordinarily required. If the air conditioner is used in a dirty environment, periodic 

cleaning of dirt and debris from the outside fin surface may be required to maintain design operating 

performance. Care must be taken during cleaning to prevent damage to the coil fins.

CONDENSER INLET FILTER

Periodic maintenance of the inlet filter will assure normal operation of your air conditioner.
As the compressors operating temperature increases above normal due to dirty or clogged inlet filter (or 

plugged condenser coil), it will stop operating due to actuation of the thermal overload cut−out switch 

located on the compressor housing. As soon as the compressor temperature has dropped to within 

the switch’s cut−in setting, the compressor will restart automatically. However,the above condition will 

continue to take place until the inlet filter has been cleaned or replaced. It is recommended that the power 

to the air conditioner be disconnected when abnormally high compressor operating temperatures cause 

automatic shut−down of the unit. The above described shutdown is symptomatic of clogged or dirty filters, 

thus causing a reduction in cooling air flow across the surface of the compressor and condenser coil.

Continued operation of the air conditioner with a clogged or dirty filter will damage and 

shorten the compressor life. The air conditioner features an easily removable inlet filter to 

facilitate necessary cleaning.

Summary of Contents for PAC216T66

Page 1: ... 2016 Pentair Equipment Protection 87567377 Rev E P N 11359799 PROLINE Top Mount Air Conditioner 2000 4000 BTU Hr INSTRUCTION MANUAL ...

Page 2: ...ure to do so may result in damage to the unit or other enclosure equipment The air conditioner power source should be electrically isolated from all other sources to the enclosure equipment This is particularly important if any of the equipment is susceptible to noise or voltage fluctuations which may be encountered during air conditioner start up CAUTION TABLE OF CONTENTS Introduction 2 Design Da...

Page 3: ...0 1172 125 52 140 63 R134A 13 0 PAC426T68 23 31 x 23 61 592 x 400 230 50 60 8 0 7 5 4000 1172 125 52 140 63 R134A 13 0 PAC416T86 31 19 x 15 75 792 x 400 115 50 60 14 7 13 6 4000 1172 125 52 140 63 R134A 13 0 PAC426T86 31 19 x 15 75 792 x 400 230 50 60 8 0 7 5 4000 1172 125 52 140 63 R134A 13 0 PAC416T88 31 19 x 23 61 792 x 400 115 50 60 14 7 13 6 4000 1172 125 52 160 72 R134A 13 0 PAC426T88 31 19 ...

Page 4: ...ore operating in order to allow the compressor oil to drain to the compressor sump area NEVER attempt to operate the air conditioner while in any other position than the operating position Running the refrigeration compressor without oil in the lower part of the housing will cause permanent damage to the unit This also voids the warranty CAUTION PRODUCT IDENTIFICATION For installation and maintena...

Page 5: ...perature measuring device The cool air output should be between 50 F to 60 F when room temperature is between 70 F to 80 F These units are equipped with a thermostat If the thermostat is not set properly the condenser fan and compressor may not operate while the evaporator fan runs If this condition exists the entering air temperature to the evaporator may be below the thermostat setpoint To corre...

Page 6: ... all internal and external electrical clearances to ensure equipment will function safely and properly CAUTION 1 Remove cover from PROLINE frame 2 Remove shroud from air conditioner Four bolts and washers at the top of the air conditioner Two screws in the front flange 3 Place the air conditioner base on top of the PROLINE frame 4 Use four bolts and washers to fasten air conditioner base to the to...

Page 7: ...nly generally available in any reputable air conditioning repair or service company in your local area Refer to the data on your nameplate which specifies the type of refrigerant and the charge sizes in ounces Prior to recharging the system must be evacuated and checked for leaks FANS AND MOTORS Fan motors require no maintenance All bearings shafts etc are lubricated during manufacturing for the l...

Page 8: ...ons in operating duty cycles of the air conditioner Amounts of airborne dust dirt particles are different in every location It is recommended that when a fine layer of dust or lint is visible on the surface of the filter it should be flushed drained coated with proper adhesive and reinstalled Do not run the air conditioner for an extended period of time with the inlet filter removed Particles of d...

Page 9: ... 1106 101 10 1106 101 Filter Air Reusable Wide N S 10 1000 56 10 1000 56 10 1000 56 10 1000 56 Filter Dryer 7 52 6028 00 52 6028 00 52 6028 00 52 6028 00 Grille Front Wide N S 10 1130 00 10 1130 00 10 1130 00 10 1130 00 Hot Gas By Pass Valve 8 52 6027 16 52 6027 16 52 6027 16 52 6027 16 Pan Condensate 9 10 1130 24 10 1130 24 10 1130 24 10 1130 24 Pan Evaporator 10 10 1130 11 10 1130 11 10 1130 11 ...

Page 10: ...ir Equipment Protection label affixed to product without written Pentair Equipment Protection approval Pentair Equipment Protection must be notified of a claim in writing not later than fourteen 14 days from the date when Buyer has become aware of such occurrence or where the defect is such that it may cause damage immediately such notice containing a description of how the defect manifests itself...

Page 11: ...is fee If approval is not received within 30 days material will be scrapped and all shipping expenses and corresponding analysis fees will be billed to Buyer E At Buyer s request Failure Analysis can be provided by Pentair Equipment Protection for warrantable goods at no charge Failure analysis for non warranty repairs are subject to a 150 per hour Engineering charge plus any other incurred testin...

Page 12: ... 2016 Pentair Equipment Protection 87567377 Rev E P N 11359799 Pentair Equipment Protection 2100 Hoffman Way Minneapolis MN 55303 USA 1 763 422 2211 1 763 576 3200 PentairProtect com ...

Reviews: