3 MOUNTING AND INSTALLATION
3.1 MOUNTING THE THERMOSTAT
NRG-Temp is intended for flush mounting in a
standard 65 mm wall box. It should be positioned
approximately 1.5 Metres above the floor, protected
from direct sunlight and draughts. All electrical
conduits passing into the wall box that contain
cables must also be sealed to protect the thermostat
against draughts, e.g. with a piece of insulation in
the conduit outlet.
±1,5
m
Figure 3
If the NRG-Temp is mounted in a wall with a rough
surface, e.g. bricks, use silicon glue to make a seal
between the wall and the thermostat frame.
Note:
The NRG-Temp can also be mounted on a wall
with a wall box.
Assembly frame and front of thermostat can be
removed by pushing gently with a screw driver on the
two fasteners located on each side of the thermostat
(see Figure 4).