7.1.3 USER MENU 3: CALIBRATION OF THE FLOOR 
TEMPERATURE (OFFSET VALUE)

To adjust the 

floor-sensor

 temperature to the real 

conditions of the floor surface, you can make an 

OFFSET to the temperature measured by the floor 

sensor (T

floor

 see User Menu 2: Service read out). 

Use a separate thermometer that you position 

on the surface of the floor (T

surface

). Once the floor 

temperature is stable, read the temperature 

on the thermometer and calculate the offset.  

OFFSET = T

floor

 - T

surface

. Fill in the OFFSET VALUE in 

this menu by using 

 

[ ]

R

C

 

EcoHome

 

 

EcoOffice

 

 

 

Standby

 

• 

0h 

• 

• 

• 

• 

• 

• 

• 

12 

• 

• 

15 

• 

• 

18 

• 

• 

21 

• 

• 

24 

• 

0h 

• 

• 

• 

• 

• 

• 

• 

12 

• 

• 

15 

• 

• 

18 

• 

• 

21 

• 

• 

24 

• 

0h 

• 

• 

• 

• 

• 

• 

• 

12 

• 

• 

15 

• 

• 

18 

• 

• 

21 

• 

• 

24 

 or

 

[ ]

R

C

 

EcoHome

 

 

EcoOffice

 

 

 

Standby

 

• 

0h 

• 

• 

• 

• 

• 

• 

• 

12 

• 

• 

15 

• 

• 

18 

• 

• 

21 

• 

• 

24 

• 

0h 

• 

• 

• 

• 

• 

• 

• 

12 

• 

• 

15 

• 

• 

18 

• 

• 

21 

• 

• 

24 

• 

0h 

• 

• 

• 

• 

• 

• 

• 

12 

• 

• 

15 

• 

• 

18 

• 

• 

21 

• 

• 

24 

 .

Possible values: 

0 to 10°C 

Factory set value: 

4°C

T

surface

Tfloor sensor

 

Figure 24

7.1.4 USER MENU 4: CALIBRATION OF THE ROOM 
TEMPERATURE (SET VALUE)

To adjust the 

room-sensor

 temperature to the real 

conditions of the room, you can use the calibration 

of the temperature set value. Use a separate 

thermometer that you position in the middle of 

the room (away from direct sunlight). Once the 

temperature is stable, read the temperature on the 

thermometer and fill in this temperature in this 

menu by using 

 

[ ]

R

C

 

EcoHome

 

 

EcoOffice

 

 

 

Standby

 

• 

0h 

• 

• 

• 

• 

• 

• 

• 

12 

• 

• 

15 

• 

• 

18 

• 

• 

21 

• 

• 

24 

• 

0h 

• 

• 

• 

• 

• 

• 

• 

12 

• 

• 

15 

• 

• 

18 

• 

• 

21 

• 

• 

24 

• 

0h 

• 

• 

• 

• 

• 

• 

• 

12 

• 

• 

15 

• 

• 

18 

• 

• 

21 

• 

• 

24 

 or 

 

[ ]

R

C

 

EcoHome

 

 

EcoOffice

 

 

 

Standby

 

• 

0h 

• 

• 

• 

• 

• 

• 

• 

12 

• 

• 

15 

• 

• 

18 

• 

• 

21 

• 

• 

24 

• 

0h 

• 

• 

• 

• 

• 

• 

• 

12 

• 

• 

15 

• 

• 

18 

• 

• 

21 

• 

• 

24 

• 

0h 

• 

• 

• 

• 

• 

• 

• 

12 

• 

• 

15 

• 

• 

18 

• 

• 

21 

• 

• 

24 

.

All manuals and user guides at all-guides.com

Summary of Contents for NRG-Temp

Page 1: ...p IM EU0309 R0 THERMAL BUILDING SOLUTIONS 210116 Software version 3 2 pentairthermal com manuals CZ DA DE EN ES ET FI FR HU IT LT LV NL NO PL RU SV All manuals and user guides at all guides com a l l...

Page 2: ...2 82 82 57 33 70 5 70 5 Figure 1 Figure 2 All manuals and user guides at all guides com...

Page 3: ...3 6 9 12 15 18 21 24 0h 3 6 9 12 15 18 21 24 14 6 3 Automatic R C EcoHome EcoOffice Standby 0h 3 6 9 12 15 18 2 0h 3 6 9 12 15 18 2 15 6 3 1 In Comfort Program 15 6 3 2 In Economic Programs EcoH EcoO...

Page 4: ...t for the floor sensor 24 7 1 8 User Menu 8 Minimum temperature set point for the room sensor 24 7 1 9 User Menu 9 Maximum temperature set point for the room sensor 25 7 2 The Installers or Advanced U...

Page 5: ...This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and knowledge if they have been given supervi...

Page 6: ...rammable Timer Thermostat that is preloaded with 4 programs see Table 1 Program Name Description Symbol Comfort Program In the Comfort Program the NRG Temp is aiming for 1 temperature only called the...

Page 7: ...od comfort feeling when being present in the room R C EcoH EcoO Stan Booster Temperature Sometimes it can be interesting to give a boost to your underfloor heating The booster function will raise your...

Page 8: ...o protect the thermostat against draughts e g with a piece of insulation in the conduit outlet 1 5 m Figure 3 If the NRG Temp is mounted in a wall with a rough surface e g bricks use silicon glue to m...

Page 9: ...on of the thermostat For best control performance position the floor sensor between two heating cables as close as possible to the top floor surface Do not position the floor sensor tip closer than 3...

Page 10: ...ntegrated suppression device Do not use contactor without interference filter Figure 6 If you connect multiple heating cables you must use a contactor Normally Open with integrated suppression device...

Page 11: ...he floor sensor must be installed and activated for any installation with T2QuickNet 3 4 2 NRG TEMP WITH THE T2RED T2REFLECTA SELF REGULATING CABLE Self regulating heating cables have an inrush curren...

Page 12: ...8 21 24 1 I I 7 Figure 9 In this program the NRG Temp is set to the default Comfort temperature of 23 C Use R C EcoHome EcoOffice Standby 0h 3 0h 3 or R C EcoHome EcoOffice Standby to adapt the temper...

Page 13: ...uare around the function icon 0h 3 6 9 12 15 18 21 24 1 I I 7 0h 3 6 9 12 15 18 21 24 1 I I 7 0h 3 6 9 12 15 18 21 24 1 I I 7 0h 3 6 9 12 15 18 21 24 0h 3 6 9 12 15 18 21 24 1 I I 7 0h 3 6 9 12 15 18...

Page 14: ...fice Standby 0h 3 6 9 0h 3 6 9 0h 3 6 9 12 15 18 21 24 Reduced Temperature R C EcoHome EcoOffice Standby 0h 3 6 9 0h 3 6 9 Clock R C EcoHome EcoOffice Standby 0h 3 6 9 0h 3 6 9 Program Choice R C EcoH...

Page 15: ...rn automatically to R C EcoHome EcoOffice Standby 0h 3 6 9 12 15 18 21 24 0h 3 6 9 12 15 18 21 24 0h 3 6 9 12 15 18 21 24 after the first timer event 6 2 REDUCED TEMPERATURE R C EcoHome EcoOffice Stan...

Page 16: ...18 21 24 0h 3 6 9 12 15 18 21 24 The Booster is a function used to deviate from the Comfort temperature during a period of 2 hours If you activate the Booster your NRG Temp thermostat will be set for...

Page 17: ...rogram the Thermostat is set to the default temperature Use R C EcoHome EcoOffice Standby 0h 3 6 9 12 15 18 21 0h 3 6 9 12 15 18 21 or R C EcoHome EcoOffice Standby 0h 3 6 9 12 15 0h 3 6 9 12 15 to ad...

Page 18: ...educed R C EcoHome EcoOffice Standby 0h 3 6 9 12 15 18 21 24 0h 3 6 9 12 15 18 21 24 0h 3 6 9 12 15 18 21 24 33 00 06 12 18 24 02 04 16 14 10 08 20 22 00 06 12 18 24 02 04 16 14 10 08 20 22 00 06 12 1...

Page 19: ...6 9 12 15 18 21 24 R C EcoHome EcoOffice Standby 0h 3 6 9 12 0h 3 6 9 12 0h 3 6 9 12 15 18 21 24 R C EcoHome EcoOffice Standby 0h 3 6 9 12 15 18 21 24 0h 3 6 9 12 15 18 21 24 Figure 16 IMPORTANT Using...

Page 20: ...and 24 hours with 30 minutes steps Step 3 B Programming the other timeslots Repeat Step 3 A until you have reached the 24 00 hours Step 4 Programming Day 2 to 7 You can either copy the previous day or...

Page 21: ...Office Standby 0h 3 6 9 12 15 18 21 24 0h 3 6 9 12 15 18 21 24 0h 3 6 9 12 15 18 21 24 D Adjustable switching hysteresis R C EcoHome EcoOffice Standby 0h 3 6 9 12 15 18 21 24 0h 3 6 9 12 15 18 21 24 0...

Page 22: ...24 1 I I 7 0h 3 6 9 12 15 18 21 24 0h 3 6 9 12 15 18 21 24 1 I I 7 Figure 22 By using R C EcoHome EcoOffice Standby 0h 3 6 9 12 15 18 21 24 0h 3 6 9 12 15 18 21 24 or R C EcoHome EcoOffice Standby 0h...

Page 23: ...C EcoHome EcoOffice Standby 0h 3 6 9 12 15 18 21 24 0h 3 6 9 12 15 18 21 24 or R C EcoHome EcoOffice Standby 0h 3 6 9 12 15 18 21 24 0h 3 6 9 12 15 18 21 24 Possible values 0 to 10 C Factory set valu...

Page 24: ...to change the temperature in the Comfort R C EcoHome EcoOffice Standby 0h 3 6 9 12 15 18 21 24 0h 3 6 9 12 15 18 21 24 0h 3 6 9 12 15 18 21 24 Auto R C EcoHome EcoOffice Standby 0h 3 6 9 12 15 18 21 2...

Page 25: ...E ROOM SENSOR You can define a maximum temperature set point It is then not possible to change the temperature in the Comfort R C EcoHome EcoOffice Standby 0h 3 6 9 12 15 18 21 24 0h 3 6 9 12 15 18 21...

Page 26: ...ruption the thermostat will continue the First Warming function when the power is restored This function can be stopped at any time by setting the installer menu B to OFF Possible values ON OFF Factor...

Page 27: ...rost Protection menu Fixed set point 7 C Possible values ON OFF Factory set value OFF 7 2 7 USER MENU G PROPORTIONAL REGULATION In room sensing mode the proportional regulation reduces the temperature...

Page 28: ...2 KEY LOCK FEATURE It is possible to lock the keys of the NRG Temp thermostat 8 2 1 LOCK Press and hold all buttons simultaneously The key symbol R C EcoHome EcoOffice Standby 0h 3 6 9 12 15 18 21 24...

Page 29: ...one of the temperature sensors the heating output cuts off fail safe and an error code is displayed The floor sensor may be replaced by a new one product reference 1244 002952 In the event of malfunc...

Page 30: ...lar white RAL 9010 Display LCD with blue backlight Control modes Floor sensor 5 35 C Room sensor 5 40 C Room sensor with floor sensor as a limiter Room temperature control accuracy EN15500 CA 0 7K eu...

Page 31: ...31 12 APPROVALS AND DECLARATIONS 210116 All manuals and user guides at all guides com a l l g u i d e s c o m...

Page 32: ...ICH Tel 0800 297410 Fax 0800 297409 info ptm at pentair com POLSKA Tel 48 22 331 29 50 Fax 48 22 331 29 51 salespl pentair com 7 495 926 18 85 7 495 926 18 86 salesru pentair com SCHWEIZ SUISSE Tel 08...

Reviews: