background image

Page 4

Pentair Water Commercial Pool and Spa

All boilers must be installed on a non-combustible

floor. Under no circumstances can boilers be installed
on carpeting. The National Fuel Code allows a boiler
to be placed on other than a non combustible surface
when such an installation complies with the local
codes. This code specifies the surface under the boiler
be protected with hollow masonry no less than 4" thick,
covered with sheet metal at least 20 gage in thickness.
Such masonry must be laid with ends unsealed, and
joints matched in such a way as to provide a free
circulation of air from side to side through the masonry
(see Figure 2).

cause accelerated deterioration of controls and
electrical components.

3.

Exhaust Fans or Vents: Any equipment which
exhausts air from the boiler room can deplete the
combustion air supply or reverse the natural draft
action of the venting system. This could cause
flue products to accumulate in the room.
Additional air must be supplied to compensate
for such exhaust. The information in Table 2 is
not applicable in installations where exhaust
fans or blowers of any type are used. Such
installations must be designed by qualified
engineers.

Figure 2. Non-Combustible Base.

2B. Installation of Indoor Boilers

2B-1. Combustion Air Supply

1.

The boiler location must provide sufficient air
supply for proper combustion, and ventilation of
the surrounding area as outlined in the latest
edition of ANSI standard Z223.1 or, in Canada
CAN1-B149, and any local codes that may be
applicable. Inadequate combustion air supply
may result in incomplete combustion and
consequent sooting of the heat exchange and
unsafe operation of the boiler.

2.

In general, (in the U.S.), these requirements
specify that equipment rooms which represent
confined spaces should be provided with two
permanent air supply openings communicating
directly through the wall to outside air; one
within 12 inches of the ceiling, the other within
12 inches of the floor. Each opening should have
a minimum free area of one square inch per
4,000 BTUH input of the total input rating of all
appliances in the enclosed area. These
requirements differ in Canada. Consult the
National Standard of Canada CAN1-B149 for
details. See Table 2 for recommended air supply
for U.S. models. An improperly ventilated
equipment room can get excessively hot and

Clearance

Indoor

Outdoor

From

(Inches)

(Inches)

Top

24

Water Conn. Side

24

24

Opposite Side

24

24

Front

48

48

Rear

24

24

Vent

6

Table 1. Minimum Boiler Clearance

From Combustible Surfaces

Indoor

Each Opening*

Size

(Square Inches)

2000

500

2450

613

3050

763

3500

875

4050

1013

4500

1125

5000

1250

Net Free Area in Square Inches*

*Area indicated is for one of two openings: one at floor level
and one at the ceiling, so the total net free area would be
double the figures indicated. For all other conditions, refer to
latest edition of ANSI A223.1.

NOTE: Check with louver manufacturers for Net Free Area of
louvers. Correct for screen resistance to the Net Free Area if
a screen is installed. Check all local codes applicable to
combustion air.

Table 2. Minimum Recommended Air

Supply to Equipment Room.

4.

If a blower or fan is used to supply air to the
equipment room, the installer should make sure it
does not create drafts which could cause
nuisance shut-downs of the pilot. If a blower is
necessary to provide adequate combustion air to
the boiler, a suitable switch or equivalent must
be wired into the boiler control circuit to prevent
the boiler from firing unless the blower is
operating.

5.

The boiler must be completely isolated and
protected from any source of corrosive chemical
fumes such as emitted by trichlorethylene,
perchlorethylene, chlorine, etc.

Blocks must provide solid base and be braced so they cannot
slip out of place. Air openings in blocks must be arranged to
provide unobstructed opening through entire width or length of
base.

Summary of Contents for MegaTherm MT 2000

Page 1: ...sult causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL G...

Page 2: ...it Checkout 10 3B To Start Up System See Section 3A for Initial Start Up 10 3C To Turn Off Boiler 10 3D Spring and Fall Operation 10 3E WinterOperation 10 3E 1 DrainingBoilerBeforeFreezing 10 3E 2 Imp...

Page 3: ...the Pentair Water Commercial Pool and Spa technical support see page 2 or your local representative with any problems or questions regarding this equipment Experience has shown that most operating pr...

Page 4: ...unicating directly through the wall to outside air one within 12 inches of the ceiling the other within 12 inches of the floor Each opening should have a minimum free area of one square inch per 4 000...

Page 5: ...al draft action of the venting system This can create a health hazard by spilling flue products into the boiler room 6 Avoid oversize vent piping or extremely long runs of the pipe which may cause exc...

Page 6: ...essure could be an indication of an undersized gas meter and or obstructed gas supply line 6 The correct burner manifold gas pressure is stamped on the rating plate The regulator is preset at the fact...

Page 7: ...Piping of System to Boiler 1 Be sure to provide gate valves at the inlet and outlet to the boiler so it can be readily isolated for service 2 The pressure relief valve must be installed in the tapped...

Page 8: ...ic flow control valve will maintain proper flow through the boiler regardless of the reduced water flow due to a dirty or clogged filter 2J Automatic Chlorinators A concentration of chlorine in the bo...

Page 9: ...tch on the boiler is in the ON position After placing the manual pilot valves in the open position and resetting all safety devices high limit pressure switch Low Water Cutoff etc pilots can be lit fo...

Page 10: ...pool water temperature automatically 3C To Turn Off Boiler 1 Turn off main electrical switch 2 Close all manual gas valves 3D Spring and Fall Operation When the pool is not going to be used for a lon...

Page 11: ...eriodic Service Inspect the heat exchanger tubes of the Model MT pool boiler on a regular basis In most areas and under most operating conditions the MT pool boiler will operate for years without accu...

Page 12: ...Reassemble in reverse order Be sure to replace the heat exchanger baffles 6 The gas and electric controls installed on the boilers are designed for both dependable operation and long life But the safe...

Page 13: ...is indicated replace coil or operator Boiler is Pounding Knocking or Emitting Steam from Relief Valves Possible Cause What To Do Lower or no water flow This condition is usually caused by lack of adeq...

Page 14: ...and remaining screws from flue collector extension 12 12 Install middle rear panel 13 13 Install front panel making sure opening for removable panel is square 19 14 Install front stiffener 184 2450 an...

Page 15: ...MegaTherm Commercial Pool Heating Boiler Page 15 Figure 12 Outdoor Parts Referenced on page 14...

Page 16: ...sembly 20011301 20011302 20011303 20011304 20011305 20011306 20011307 12 Rear Closure Assembly 20012401 20012402 20012403 20012404 20012405 20012406 20012407 13 Heat Shield Support Bracket 20003201 20...

Page 17: ...MegaTherm Commercial Pool Heating Boiler Page 17 Figure 13 Parts Identification Indoor parts only For tiles see Figure 15...

Page 18: ...20012303 20012304 20012305 20012306 20012307 indoor only 35 Flue End Assembly 20012000 20012000 20012000 20012000 20012000 20012000 20012000 2 2 2 2 2 2 2 36 Upper End Assembly 20011900 20011900 2001...

Page 19: ...shown 2 2 2 2 2 49 b Pilot Relay Standing Pilot W003000 W003000 W003000 W003000 W003000 W003000 W003000 not shown 2 2 2 2 2 50 Pilot Burner Johnson W0034700 W0034700 W0034700 W0034700 W0034700 W00347...

Page 20: ...1 805 553 5000 Trademarks and disclaimers MegaTherm and the Pentair Commercial Pool and Spa logo are trademarks of Pentair Water Pool and Spa Inc Other trade marks and trade names may be used in this...

Reviews: