background image

MegaTherm Commercial Pool Heating Boiler

Page 13

SECTION 5.
Troubleshooting and Analysis of
Service Problems

1.

For proper service and problem diagnosis of the
boiler and system, the following tools are
required:

a.

Gas pressure test kit with range from zero
to 14" W.C. Either a slack tub manometer
or an accurate gas pressure gauge is
acceptable with proper adaptors which will
connect to the available fittings in the line
and on the gas valve.

b.

Electric meter(s) with the following ranges:

0 to 500 volts A.C.
0 to 1000 ohms continuity.

c.

Millivolt meter with the following ranges:

0 to 50 millivolts. 0 to 500 millivolts.
0 to 1000 millivolts.

d.

Tube cleaning kit consisting of reamer,
stainless steel brush, speed handle and
handle extensions.

e.

Accurate thermometer and pressure gauge.

2.

In addition, the boiler should be equipped with a
thermometer with proper ranges.

Boiler Will Not Fire

Possible Cause

What To Do

Electric Power
is off.

Check to see that main power switch
is ON. Use testing device to trace
power to boiler junction box.

Operating or
safety control has
opened circuit to
electric gas valve.

Turn off power. Use continuity tester
to check continuity across terminals of
each operating and safety control
switch up to the electric gas valve.
Replace defective control.

Pilot flame is out.

Relight pilot per instructions.

Manual reset
device has
tripped.

Follow instructions for start-up. Reset
pilot safety and all manual reset
safety switches.

No gas pressure to
burners.

Trace gas line to service shutoff cock.
If service cock is open, trace gas line
to meter. If no pressure is present at
meter, call for public utility service. If
gas is present in heater inlet, check
pressures in following sequence:
(1) downstream from pressure
regulator,
(2) downstream from electric gas
valve. Replace or adjust as
necessary.

Electric gas valve
operator is burned
out or shortened.

Disconnect wiring harness at gas
valve terminals. Check continuity to
actuator coil. If open circuit or short is
indicated, replace coil or operator.

Boiler is Pounding, Knocking,

or Emitting Steam from Relief Valves

Possible Cause

What To Do

Lower or no water
flow.

This condition is usually caused by
lack of adequate water flow through
heater. check the following:
1. Is the heater wired into the pump
circuit so that the heater cannot fire
unless the pump is running?
2. Check to see that all valves in
system are open to be sure that water
can circulate through the heater and
the system.
3. Examine pump for clogged
impeller.
4. Check water filter.

Debris from system
is blocking tubes.

Remove header covers. Examine all
tubes and waterways. Use new
gaskets when reassembling. Clean
out tubes.

Scale has formed
in tubes.

This is always caused by heavy
mineral content of the water or
clogged filter. Check the water
chemistry. Replace the filter and
clean all the internal wet surfaces.

Soot in Flueways or in Tubes, or Noxious

Fumes Indicative of Bad Combustion

Possible Cause

What To Do

Combustion air
supply to
equipment room is
inadequate.

Check air supply opening. Look for
debris in screen or louvre which
covers combustion air opening, or for
material blocking the opening.

Stack or vent is
blocked or
restrictive.

Look for blocked stack and excessive
number of elbows in stack or
excessive length of horizontal runs.

Severe down draft
is causing spillage
of flue products
into room.

Check for (1) proper vent cap on
stack; (2) adequate height of stack
above roof; (3) equipment exhausting
air from inside of building.

Gas pressure to
burners is
excessive.

Check gas pressure with
manometer,and adjust with heater
firing at full rate.

Heater not fitted
for the fuel being
supplied.

See nameplate for correct fuel.

Heater installed at
high altitude
without proper
derating.

Installations at altitudes in excess of
2000 ft. above sea level are subject
to jurisdiction of the local inspection
authorities. Check with the factory.

Water Dripping in Firebox

Possible Cause

What To Do

Tube in heat
exchanger has
overheated and
ruptured.

A tube failure is almost always
caused by:
(a) Scale formation in the tube, or:
(b) inadequate water flow through the
boiler.
Replace heat exchanger tube(s) and
check for proper flow.

Summary of Contents for MegaTherm MT 2000

Page 1: ...sult causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL G...

Page 2: ...it Checkout 10 3B To Start Up System See Section 3A for Initial Start Up 10 3C To Turn Off Boiler 10 3D Spring and Fall Operation 10 3E WinterOperation 10 3E 1 DrainingBoilerBeforeFreezing 10 3E 2 Imp...

Page 3: ...the Pentair Water Commercial Pool and Spa technical support see page 2 or your local representative with any problems or questions regarding this equipment Experience has shown that most operating pr...

Page 4: ...unicating directly through the wall to outside air one within 12 inches of the ceiling the other within 12 inches of the floor Each opening should have a minimum free area of one square inch per 4 000...

Page 5: ...al draft action of the venting system This can create a health hazard by spilling flue products into the boiler room 6 Avoid oversize vent piping or extremely long runs of the pipe which may cause exc...

Page 6: ...essure could be an indication of an undersized gas meter and or obstructed gas supply line 6 The correct burner manifold gas pressure is stamped on the rating plate The regulator is preset at the fact...

Page 7: ...Piping of System to Boiler 1 Be sure to provide gate valves at the inlet and outlet to the boiler so it can be readily isolated for service 2 The pressure relief valve must be installed in the tapped...

Page 8: ...ic flow control valve will maintain proper flow through the boiler regardless of the reduced water flow due to a dirty or clogged filter 2J Automatic Chlorinators A concentration of chlorine in the bo...

Page 9: ...tch on the boiler is in the ON position After placing the manual pilot valves in the open position and resetting all safety devices high limit pressure switch Low Water Cutoff etc pilots can be lit fo...

Page 10: ...pool water temperature automatically 3C To Turn Off Boiler 1 Turn off main electrical switch 2 Close all manual gas valves 3D Spring and Fall Operation When the pool is not going to be used for a lon...

Page 11: ...eriodic Service Inspect the heat exchanger tubes of the Model MT pool boiler on a regular basis In most areas and under most operating conditions the MT pool boiler will operate for years without accu...

Page 12: ...Reassemble in reverse order Be sure to replace the heat exchanger baffles 6 The gas and electric controls installed on the boilers are designed for both dependable operation and long life But the safe...

Page 13: ...is indicated replace coil or operator Boiler is Pounding Knocking or Emitting Steam from Relief Valves Possible Cause What To Do Lower or no water flow This condition is usually caused by lack of adeq...

Page 14: ...and remaining screws from flue collector extension 12 12 Install middle rear panel 13 13 Install front panel making sure opening for removable panel is square 19 14 Install front stiffener 184 2450 an...

Page 15: ...MegaTherm Commercial Pool Heating Boiler Page 15 Figure 12 Outdoor Parts Referenced on page 14...

Page 16: ...sembly 20011301 20011302 20011303 20011304 20011305 20011306 20011307 12 Rear Closure Assembly 20012401 20012402 20012403 20012404 20012405 20012406 20012407 13 Heat Shield Support Bracket 20003201 20...

Page 17: ...MegaTherm Commercial Pool Heating Boiler Page 17 Figure 13 Parts Identification Indoor parts only For tiles see Figure 15...

Page 18: ...20012303 20012304 20012305 20012306 20012307 indoor only 35 Flue End Assembly 20012000 20012000 20012000 20012000 20012000 20012000 20012000 2 2 2 2 2 2 2 36 Upper End Assembly 20011900 20011900 2001...

Page 19: ...shown 2 2 2 2 2 49 b Pilot Relay Standing Pilot W003000 W003000 W003000 W003000 W003000 W003000 W003000 not shown 2 2 2 2 2 50 Pilot Burner Johnson W0034700 W0034700 W0034700 W0034700 W0034700 W00347...

Page 20: ...1 805 553 5000 Trademarks and disclaimers MegaTherm and the Pentair Commercial Pool and Spa logo are trademarks of Pentair Water Pool and Spa Inc Other trade marks and trade names may be used in this...

Reviews: